![Wayne Reliance G6101D Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/wayne/reliance-g6101d/reliance-g6101d_installation-and-operation-manual_3948334012.webp)
8
920943 Rev E July 2014
2.6
Remote Dispenser Applications
To maximize flow, position the remote dispenser and tank as close together as possible and
minimize the number of turns in the piping. Consult the submersible pump manufacturer for
the proper sizing of the submersible pump, any necessary leak detection equipment, and
installation details.
Product piping must avoid the creation of vapor in the lines and deliver a minimum pressure
of 25 psi at the remote dispenser inlet when all dispensers connected to the same
submersible pump are operating. The dispenser’s maximum operating pressure is 50 psi.
A UL Listed, rigidly anchored emergency shutoff valve must be installed, in accordance with
the manufacturer’s instructions, in each supply line at the base of each dispenser.
NOTE: On E85 dispenser models, use shear valve part number 10P-0152E85 manufactured by
OPW.
WARNING
Содержание Reliance G6101D
Страница 8: ...4 920943 Rev E July 2014...
Страница 20: ...16 920943 Rev E July 2014...
Страница 24: ...20 920943 Rev E July 2014...
Страница 32: ...28 920943 Rev E July 2014...
Страница 33: ...920749 Rev G 7 2014 29 APPENDIX A DIMENSIONS BASE LAYOUTS...
Страница 36: ...32 920749 Rev G 7 2014 Rotate Upwards 26 301 4 Hose Mast Dimensions...
Страница 40: ...36 920749 Rev G 7 2014...