Wayne P250 series Скачать руководство пользователя страница 13

13

LP gas is heavier than air and will settle in low lying areas such

as combustion chambers or heat exchangers. All connections should be checked
for leaks using a soapy solution applied to gas connections.

DETERMINE ORIFICE SIZE AND RATE

The gas conversion burner needs to be set to deliver the same amount of heat to the appliance as the oil burner it is replaci ng.
Determine the Btu/hr heat input rate for the appliance by locating the rating plate of the appliance and determine the firing rate
of the oil burner. Typically the nozzle in the oil burner is stamped with the gallon per hour rate. Use the lesser of these t wo
rates as the firing rate of the gas burner.

For calculating from gallon/hour of oil to Btu/hour of gas, One gallon of oil produces 140,000 Btu/gal (147700 kJ/L) of heat. For
example: A furnace rating of 0.60 G.P.H. would be 0.60 x 140,000 = 84,000 Btu/hr. This is the input rate needed from the gas
burner.

Once the desired heat output of the burner has been determined, the gas orifice must be properly sized. The gas orifice
factory installed in all burners is sized to produce the minimum firing rate of the burner; 50,000 Btu/hr for the P250, 65,000
Btu/hr for the P265.

To determine the proper orifice size for the application, refer to Table 4 below. Locate the drill size by selecting the proper
column based on the gas to be used. Example: To fire 80,000 Btu/hr on natural gas requires an orifice drilled with a #19 drill
bit (0.166”).

NOTE: Numbered and lettered drill bit sizes are valid bit sizes. They are machinist’s drill bits. Decimal values have
been provided in Table 4 as assistance in determining closest fractional drill bit size to the number/letter drill bit size.

The correct manifold pressure for natural gas is 3.5” w.c (872 Pa). Only minor adjustments in the input rate should be made by
adjusting the pressure regulator. The minimum manifold pressure should be 3.0” w.c. (747 Pa) and the maximum pressure
should be 3.5” w.c. (872 Pa). The next size larger or smaller orifice size should be used if the desired input rating cannot be
obtained within the above manifold pressure adjustment range.

The correct manifold pressure for L.P. gas is 10” w.c. (2491 Pa). Only minor adjustments in the input rate should be made by
adjusting the pressure regulator. The minimum manifold pressure should be 9.5” w.c. (2366 Pa), the maximum pressure 10.0”
w.c. (2491 Pa). If the desired input rating cannot be obtained within the above manifold pressure and adjustment range then
the next size larger or smaller orifice size should be used.

Table 4: Orifice Size and Drill Bit Chart

Btu/hr(Kw) Input

Natural Gas:

3.5” w.c. (872 Pa)

Propane Gas:

10” w.c. (2491 Pa)

Number/ Letter/Fraction

Decimal (in)

Number/Fraction

Decimal (in)

50,000 (15)

29

0.136

45

0.082

60,000 (18)

28 (9/64)

0.1405

44

0.086

65,000 (19)

26

0.147

43

0.089

70,000 (21)

24

0.152

3/32

0.094

75,000 (22)

5/32

0.1562

40

0.098

80,000 (23)

19

0.166

37

0.104

100,000 (29)

17 (11/64)

0.173

35 (7/64)

0.110

110,000 (32)

14

0.182

31

0.120

115,000 (34)

3/16

0.187

3.1 mm

0.122

130,000 (38)

5 (13/64)

0.2055

1/8

0.125

140,000 (41)

4

0.209

30

0.1285

150,000 (44)

7/32

0.2188

29

0.136

160,000 (47)

1

0.228

28 (9/64)

0.1405

170,000 (50)

15/64

0.2344

27

0.144

175,000 (51)

B

0.238

26

0.147

185,000 (54)

1/4

0.250

25

0.150

200,000 (59)

G

0.261

22 (5/32)

0.157

210,000 (62)

17/64

0.266

20

0.161

220,000 (64)

I

0.272

19

0.166

235,000 (69)

9/32

0.281

11/64

0.172

250,000 (73)

M (19/64)

0.295

16

0.177

Содержание P250 series

Страница 1: ...MENT CSA CERTIFICATE NUMBER 1156769 MODELS WAYNE COMBUSTION SYSTEMS 801 GLASGOW AVE FORT WAYNE IN 46803 PHONE 260 425 9200 855 WAYNECS 800 443 4625 FAX 260 424 0904 www waynecombustion com ALL P250 AN...

Страница 2: ...NSTALLER S NAME CONTRACTOR NAME CONTRACTOR ADDRESS CONTRACTOR PHONE NUMBER CONTRACTOR LICENSE DATE OF INSTALLATION COMMENTS ABOUT INSTALLATION START UP THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE BURN...

Страница 3: ...E RULES TO AVOID ELECTRIC SHOCK Use only a properly grounded circuit A ground fault interrupter is recommended Do not spray water directly on burner Turn off power before servicing Read the owner s ma...

Страница 4: ...ALLATION OF THERMOSTAT SECTION II INITIAL START UP A OPERATION OF BURNER DIRECT IGNITION B OPERATION OF BURNER ELECTRONIC PILOT C OPERATION OF BURNER STANDING PILOT D COMBUSTION ADJUSTMENT OF BURNER E...

Страница 5: ...SHOOTING AND DIAGNOSIS 31 G MORE SERVICE HINTS 32 H P250AF P265F IGNITOR POSITION 33 I P250AF P265F WIRING DIAGRAMS 34 SECTION VI PARTS LIST AND EXPLODED VIEWS 39 A P265F EXPLODED VIEWS 39 B P265F PAR...

Страница 6: ...er rooms provisions shall be made for supplying air for combustion through special openings one near the floor line and the other near the ceiling each to be sized on the basis of one square inch or m...

Страница 7: ...tch or low water cut off inspection shall determine whether either device can be utilized in the gas burner control circuit reference should be made to the American Society of Heating Refrigerating an...

Страница 8: ...e of the draft hood where permitted by local building codes If an oil barometric damper has been previously installed this may be used if it is in good condition and any and all weights and or stops a...

Страница 9: ...square inch 645 2 mm 2 of the flue area Input Btu hr Kw Draft Hood and Flue Pipe Size Up to 120 000 35 120 000 35 17 180 000 53 180 000 52 75 250 000 73 5 inch 127 mm 6 inch 152 mm 7 inch 178 mm NOTE...

Страница 10: ...checked to make sure they are in good working condition When converting oil designed boilers and furnaces it is recommended that the existing combustion chamber be used with the gas burner provided it...

Страница 11: ...645 10 25 4 x 10 25 4 210 000 62 122 787 11 27 9 x 11 27 9 240 000 70 144 929 12 30 5 x12 30 5 250 000 76 156 1008 12 31 8 x 12 31 8 Table 2 Combustion Chamber for P265 Only Input Btu hr kW Floor Area...

Страница 12: ...ily accessible for inspection cleaning adjustment and repairs INSTALLATION OF MOUNTING FLANGE Position the mounting flange on the furnace wall adjusting orientation as necessary until the bolt pattern...

Страница 13: ...ble 4 as assistance in determining closest fractional drill bit size to the number letter drill bit size The correct manifold pressure for natural gas is 3 5 w c 872 Pa Only minor adjustments in the i...

Страница 14: ...is 4 5 w c 1121Pa for natural gas and 11 0 w c 2740Pa for L P gas The maximum gas supply pressure is 10 5 w c 2615Pa for natural gas and 13 w c 3238Pa for L P gas Valve is rated for 0 5 PSI or 14 w c...

Страница 15: ...The back side is tapered and will make lining up the drill bit easier Deburr the orifice and mark new size on orifice with permanent marker Reinstall the orifice and secure the gas pipe train to the b...

Страница 16: ...ad Inch mm 3 8 9 525 3 8 9 525 9 16 14 29 1 2 12 7 1 2 12 7 3 4 19 05 3 4 19 05 1 2 9 16 14 29 13 16 20 64 1 25 4 9 16 14 29 1 25 4 FIGURE 11 PROPER PIPING PRACTICE It is recommended that tables 5 6 a...

Страница 17: ...based on 11 w c inlet pressure and a pressure drop of 0 5 w c Special use Piping sizing between single or second stage low pressure regulator and appliance Maximum Capacity of Pipe Size in Btu per Ho...

Страница 18: ...s pilots on other appliances ELECTRICAL WIRING OF BURNER The conversion burner is shipped completely wired It is only necessary to supply the 115 volt circuit thermostat and limit circuit All wiring m...

Страница 19: ...are not compatible with the burner operation they should be replaced with the proper controls INSTALLATION OF THERMOSTAT The thermostat should be installed on an inside wall and should be located in t...

Страница 20: ...utput This voltage produces a spark at the burner igniter sensor rod igniting the gas flowing around the electrode If flame is not detected during the trial for ignition the ignition control will go i...

Страница 21: ...gnition the ignition control will go into a lock out condition If this occurs proceed to the section titled SAFETY LOCK OUT TIME SECOND STAGE MAIN BURNER OPERATION When the pilot flame is established...

Страница 22: ...s bled out of the line The pilot can be seen by looking through the sight glass 7 Hold the red button on the valve for 60 seconds then release 8 Observe pilot if not lit SHUT OFF BURNER COMPLETELY AND...

Страница 23: ...spreader is used to shape the flame to best suit the firing chamber Depending on the firing chamber the flame spreader can be used to produce a long narrow flame or a short bushy flame FIGURE 16 FLAME...

Страница 24: ...ould be minimized with a goal of 100 ppm or less In no case should CO be above 400 ppm Stack temperatures for furnaces and boilers are recommended to be between 350 and 400 degrees Fahrenheit Tighten...

Страница 25: ...degrees above room temperature the burner should start automatically If it does not start check pilot If no flame is visible relight pilot following lighting instructions Burners with the letters DI...

Страница 26: ...The fan motor will develop 3400 rpm quickly causing the centrifugal endswitch to close The endswitch can be identified by the two red wires coming from the end cap of the fan motor 7 After the endswi...

Страница 27: ...not light Module senses Module________ Response________________________________________ flame current S8900A F Ignition spark continues pilot valve remains S8610A F open until system is reset________...

Страница 28: ...side 6 Ignition Rod Sensing Rod 7 Ignition Lead 8 T T 24 volt terminal TROUBLESHOOTING GUIDE ELECTRONIC PILOT FOR BURNERS UTILIZING HONEYWELL S8600 IGNITION CONTROL Start the system by setting the the...

Страница 29: ...oltage is okay replace gas control if not replace module NOTE If ignition control goes into lockout reset system Check continuity of ignition cable and ground wire Check flame rod Check electrical con...

Страница 30: ...the following after disconnecting voltage to the system a Check spark gap Gap should be 1 8 3 2mm 1 32 8mm form H V to ground CAUTION NEVER REPLACE THE COMPONENT BOARD WITHOUT FIRST CHECKING TO ENSURE...

Страница 31: ...pecified on manufacturer s data plate See Flame Current See 6 2 Flame not established Arcing to ground 3 No spark 4 Arcing other than across gap 1 Sensor probe incorrectly positioned in flame pattern...

Страница 32: ...Possible Reasons a Blower motor endswitch not closed which completes the 24 volt circuit to the gas primary b The blower motor is not reaching full rpm due to debris on wheel c Low voltage to the blo...

Страница 33: ...FIGURE 21 P250 DIRECT IGNITION IGNITOR POSITION 7 16 11 1 mm 1 16 1 6 mm 1 4 6 4 mm 1 16 1 6 mm 1 8 3 2 mm Gap 31 64 12 3 mm 1 16 1 6 mm 5 16 7 9 mm 1 8 3 2 mm Gap P265 DIRECT IGNITION IGNITOR POSITI...

Страница 34: ...bel all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing FIGURE 22 WIRING DIAGRAMS FOR GAS BURNER W...

Страница 35: ...35 FIGURE 23 WIRING DIAGRAMS FOR GAS BURNER WITH DIRECT IGNITION FENWAL...

Страница 36: ...36 FIGURE 24 WIRING DIAGRAMS FOR GAS BURNER WITH ELECTRONIC PILOT HONEYWELL...

Страница 37: ...37 FIGURE 25 WIRING DIAGRAMS FOR GAS BURNER WITH ELECTRONIC PILOT NO T STAT...

Страница 38: ...38 FIGURE 26 WIRING DIAGRAMS FOR GAS BURNER WITH ELECTRONIC PILOT FENWAL...

Страница 39: ...ide Exploded View of P265F Parts in Exploded View 1 Gas Valve 2 Air Shutter 3 Motor Blower 4 Transformer 5 Model Specification Label 6 Motor Relay 7 Ignition Control 8 Electrode Sensor Ground Rod Asm...

Страница 40: ...P265F Parts in Exploded View 1 Gas Valve 2 Air Shutter 3 Motor Blower 4 Transformer 5 Model Specification Label 6 Motor Relay 7 Ignition Control 8 Electrode Sensor Ground Rod Asm 9 T T Terminal 10 Or...

Страница 41: ...Base Pedestal Pkg 1 62246 004 Gas Valve EP Models Nat 1 62256 004 Gas Valve EP Models LP 1 62374 004 Gas Valve DI Models Nat 1 62374 PRO Gas Valve DI Models LP 1 62898 001 Orifice Holder Asm 1 60249...

Страница 42: ...P250AF Parts in Exploded View 1 Gas Valve 2 Air Shutter 3 Motor Blower 4 Transformer 5 Model Specification Label 6 Motor Relay 7 Ignition Control 8 Electrode Sensor Ground Rod Asm 9 T T Terminal 10 Or...

Страница 43: ...250AF Parts in Exploded View 1 Gas Valve 2 Air Shutter 3 Motor Blower 4 Transformer 5 Model Specification Label 6 Motor Relay 7 Ignition Control 8 Electrode Sensor Ground Rod Asm 9 T T Terminal 10 Ori...

Страница 44: ...Pedestal Pkg 1 62246 004 Gas Valve EP Models Nat 1 62256 004 Gas Valve EP Models LP 1 62374 004 Gas Valve DI Models Nat 1 62374 PRO Gas Valve DI Models LP 1 62898 001 Orifice Holder Asm 1 Varies Main...

Страница 45: ...warrants to those who purchase its Oil Burner Models for resale or for incorporation into a product of resale that its burner is free from defects in material and workmanship under normal use and ser...

Страница 46: ...46 NOTES...

Отзывы: