12
SIZING OF COMBUSTION CHAMBER
The following table is provided as a guideline for determining combustion chamber size and corresponding
firing rate when appliance rates are not available.
BURNER INSTALLATION
The HSG200 and HSG400 power gas burners were designed for converting oil fired furnaces and boilers. Due
consideration was given to making it as simple and easy to install and service as possible without weakening its
durability or efficiency. The burner is supplied as a completely assembled package unit.
NOTE: The burner must be installed in such a manner that all controls will be readily accessible for inspection,
cleaning, adjustment and repairs.
INSTALLATION OF MOUNTING FLANGE
Position the mounting flange on the furnace wall, adjusting orientation as necessary until the bolt pattern of the furnace
allows the flange to sit flush. (See Figure 10 for flange dimensions.)
Note the orientation of the flange and remove it so that the flange gasket may be placed between the furnace wall and
the flange. Tighten the flange to the furnace wall.
Insert the burner tube into the flange and position it per Figures 6, 7, 8. Tighten the flange onto the burner tube.
Input
Btu/hr (kW)
Preferred
Width Inches (mm) x
Length Inches (mm)
Diameter
Inches (mm)
50,000 (14.7)
7 (177.8) x 7 (177.8)
8 (203)
75,000 (22.0)
7.5 (190.5) x 7.5 (190.5)
9 (229)
100,000 (29.3)
12 (304.8) x 12 (304.8)
13 (330)
150,000 (44.0)
12 (304.8) x 15 (381)
14 (356)
200,000 (58.6)
13 (330.2) x 17 (431.8)
15 (381)
250,000 (73.3)
13 (330.2) x 18 (457.2)
16 (406)
300,000 (88.0)
13 (330.2) x 20 (508)
18 (457)
350,000 (102.6)
14 (355.6) x 21 (533.4)
20 (508)
400,000 (117.2)
15 (381) x 22 (558.8)
21 (533)
Recommended Combustion Chamber Sizes
Figure 9
Содержание HSG200
Страница 30: ...30 Figure 20 Flame Current Measurement Top Wayne control Bottom Honeywell control...
Страница 48: ...48 Figure 29 continued Junction Box Assemblies Exploded Figure 30 Motor Assembly Exploded...
Страница 49: ...49 Figure 31 Gun Assembly Exploded Figure 32 HSG Series Burner Exploded...
Страница 50: ...50 Figure 33 Outer Dimensions of HSG Series Burner 13 2 335 mm REF 7 7 in 195mm 7 in 178 mm 15 25 in 377 mm...
Страница 52: ...52 NOTES...