background image

2 of 20

WX-501-0517 • 05.22

LEDs

The faceplate of the Click 110 has four banks of LEDs. The top bank is used for detection indication, the second bank 

for fault indication, the third for menu indication, and the fourth for menu indication as well as operation states.

Detection

 1 

4

Fault

 

 

 

  

 

 

 

 

 

 

 

 

 

Menu

 PWR  MF 

TD 

RD

 1 

4

The detection indicator LEDs consist of four red LEDs numbered 1–4, each representing a channel (see the figure 

above). An illuminated LED indicates the presence of a vehicle. These indicators are dedicated to detection and 

have no other display purposes.

The fault indicator LEDs consist of four dual-color (green/yellow) LEDs numbered 1–4, each representing the 

channel with the corresponding number. 

 

Illuminated green LED –

 Indicates a no-fault condition.

 

Illuminated yellow LED –

 Indicates a fault condition which has existed for less than one minute.

 

Extinguished LED –

 Indicates a fault condition which has existed for more than one minute.

The menu indicator LEDs include two rows of LEDs (see the figure above). The lower row contains Level 1 indicators, 

while the upper row contains Level 2 indicators. Each level consists of four LEDs numbered 1–4 (left to right). Level 

1 LEDs display which menu is active. These Level 1 LEDs are dual-purpose, each indicating both menu selection as 

well as a normal operation state when not in Menu mode. The normal operation state functions include:

 

Red (PWR) –

 Indicates the presence of power to the device.

 

Blue (MF) –

 Illuminates when the master fault output is in the no-fault condition. The LED is extinguished in the 

fault condition.

 

Green (TD) –

 Indicates serial communication transmit data (from the Click 110) on either RS-485 bus 1 or RS-485 bus 2.

 

Yellow (RD) –

 Indicates serial communication receive data (to the Click 110) on either RS-485 bus 1 or RS-485 bus 2. 

Level 2 LEDs display configuration options. All level 2 LEDs are red. These LEDs are dedicated to menu operation, 

and are extinguished when the menu is not active. 

Push-buttons

The faceplate of the Click 110 features two push-buttons. The upper push-button, labeled 

Mode Switch

, is used to 

cycle through and select menu and configuration options.

The lower push-button, labeled 

Reset

, will reboot the Click 110. The Click 110 can be rebooted in any of three 

ways: via the reset switch, from the outstation via the 64 way DIN 41612, or by power cycling the device. A reboot 

is the only way to clear a latched fault condition. To reboot using the reset switch, simply press and release the 

push-button.

Содержание Click 110

Страница 1: ...1 21 24 1 1 1 0 25 28 1 1 1 1 29 32 S3 Channel Enable 4 5 6 7 8 Channel 0 SW Con g 1 1 1 2 1 3 1 4 S1 Bus 2 Baud Rate 5 6 7 8 Value 0 SW Con g 1 0 0 0 9600 1 0 0 1 19200 1 0 1 0 38400 1 0 1 1 57600 1...

Страница 2: ...s numbered 1 4 left to right Level 1 LEDs display which menu is active These Level 1 LEDs are dual purpose each indicating both menu selection as well as a normal operation state when not in Menu mode...

Страница 3: ...hain together all the cards you intend to use in your installation using short RJ 11 jumper cables 4 Connect the first Click 110 card to the SmartSensor via a surge protector such as the Click 200 222...

Страница 4: ...ction B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chan...

Страница 5: ...tion B25 No connection B26 No connection B27 No connection B28 No connection B29 DC 12 24 VDC B30 No connection B31 DC common B32 Pin Description A1 Channel 1 normally closed A2 No connection A3 Chann...

Страница 6: ...ument Configuration The Click 110 can be configured in three ways DIP switches the front panel menu and Click Supervisor These three different configuration methods can configure different sets of opt...

Страница 7: ...tstation mode Fault latch Each parameter except fault latch and outstation mode has a way to pick between Hardware Software modes If Software mode is selected the parameter must be configured using th...

Страница 8: ...If switch 1 5 is off down Software mode is selected and Click Supervisor and the front panel menu will be able to both display and change the current setting Channel enable The next parameter that ca...

Страница 9: ...output channels only four input datagram channels received from the sensor can be output by each device If you need more than four channels consider using multiple devices As shown in the table below...

Страница 10: ...configuration modes Fault latch The last option that can be configured on the DIP switches is fault latching This is configured on the third DIP switch labeled S3 using switch 8 S3 8 Note This paramet...

Страница 11: ...ower bank also function as activity status indicators These functions outlined in the Physical Features section of this document are only executed when the device is not in Menu mode In this case the...

Страница 12: ...ase how to autobaud bus 2 Mode switch action Display State None Normal operation Press and hold Channel map menu option displayed Continue holding Autobaud menu option displayed Release Autobaud menu...

Страница 13: ...ged using the DIP switches or Click Supervisor As mentioned earlier the Click 110 device receives serial datagrams from a SmartSensor These datagrams can contain many channels of detection data Becaus...

Страница 14: ...buses you will select which bus to autobaud on the Level 2 LEDs An autobaud will stop data reporting on the selected port and attempt to communicate with the SmartSensor at all supported baud rates Le...

Страница 15: ...default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on See the earlier Navigating through the Menu and the Menu Operation Example sections for how to configure this parameter Becau...

Страница 16: ...on Example sections for how to configure this parameter Because this parameter can also be set by the DIP switches you may need to ensure that the DIP switches are set to Software configuration mode i...

Страница 17: ...eptions are fault latch and outstation mode which are not reset by this option Level 1 LEDs Reset to default settings Level 2 LEDs Reset to default settings LED off Cancel and exit menu LED on See the...

Страница 18: ...ral tab lets you change general information about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Sett...

Страница 19: ...Bus 1 Lets you change the baud rate in bps of bus 1 Baud Rate for Bus 2 Lets you change the baud rate in bps of bus 2 Input Mapping Lets you assign input datagram channels received from the sensor to...

Страница 20: ...problems are detected a green circle will appear Once you have finished use the menu bar at the top of the screen to save your settings return to the Select Driver screen and more The Save menu allows...

Отзывы: