Page 13
Visual Inspection (FIRST TEST)
Information
In regard to the Device Under Test (DUT), please ensure that;
1. There is no damage or component defect to the accessories, plugs, outlet sockets
or connectors (physical).
2. There are no cracks &/or abrasions.
3. There are no exposed inner cores or conductors (flexible) and that the supply cords
are not twisted or distorted.
4. Any Fuse / Over load protection components (if fitted) are checked.
5. All labels, markings and warning indicators (of the maximum load to be connected
to the device) are legible and intact.
6. The insulation is not damaged in any way i.e. melted, cuts or abrasions. There are
no iron filings in the insulation. There is no insulation tape on the lead.
7. Any flexible cords and/or leads are effectively anchored (glands and grommets
intact).
8. All covers/guard are in place and secure as intended by the supplier/manufacturer.
9. All safety devices and systems are in good working order. (ie. overload latches &
buttons).
10. No dust &/or dirt obstructs any exhausts or ventilation outlets.
11. All controls are working properly and are secure and aligned.
Important:
IF RESULT IS A FAIL
If a Device Under Test (DUT) fails any of the above, it should be deemed to have
FAILED the Visual Test, and therefore no other tests need be performed. If this is
the case the DUT should be tagged with a danger tag and removed from service.
It is recommended by the manufacturer and distributor of this product that if a
DUT has failed a test it SHOULD NOT BE RETURNED TO SERVICE. To do so
would be considered unsafe.
THIS TEST IS TO OCCUR BEFORE ANY OTHER TEST
IS CARRIED OUT USING ANY OF THE RANGE OF
TnT APPLIANCE TESTERS.
Содержание TNT+
Страница 34: ...Page 34...
Страница 35: ...Page 35...