Double Check 

Backflow Preventer

Series 709 or 007 

(1”007 shown)

Sight Tube

EZ-TC Adaptor

EZ-TC Test Cock 3

Ball Valve 1

Ball Valve 2

EZ-TC 

Test Cock 1

EZ-TC 

Test Cock 2

EZ-TC  

Test Cock 4

Test of Check Valve No. 1

Purpose:

 To test valve No. 1 for tightness against reverse flow. 

Requirement:

 Valve must be tight against reverse flow.

1. Bleed test cocks No. 2, 3 and 4 to remove any trapped air.
2. Install sight tube in test cock 3. 
  A.  Open test cock 3 and allow water to fill the tube to the top. 

Use a tube length of at least 42 inches. This will provide 

a head of 1.5psi. Close test cock 3. When using EZ-TC 

test cocks to perform this test, close No. 1 and 2 shutoffs, 

install adaptor fitting in test cock 3 and install sight tube in 

adaptor. Slightly open shutoff valve No. 1 and allow water 

to fill the tube to the top then close No. 1 shutoff.

3. Close shutoff No. 2
4. Close shutoff No. 1
5.  Open test cock 2.  

Installing EZ-TC  adaptor opens test cock 2.

6.  Open test cock 3. EZ-TC on test cock 3 would already be 

open. The water should maintain its position in the sight tube.

  A.  If it slowly drops and simultaneously runs out through test 

cock 2, the check valve No. 1 is leaking and must be ser-

viced.

  B.  If it slowly drops and does not run out through Test Cock 

No. 2, then No. 2 ball valve has a small leak, but No. 1 

check valve is tight.

  C.  If it does not drop but there is a small leakage at test cock 

No. 2, then No. 1 ball valve has a small leak, but No. 1 

check valve is tight.

Test of Check Valve No. 2

Purpose:

  To test check valve No. 2 for tightness against reverse 

flow.

Requirement:

 Valve must be tight against reverse flow.

1.  Install sight tube in test cock 4 and fill with water as before. 

When using EZ-TC, close No. 1 and 2 shutoffs and install sight 

tube using adaptor fitting. Fill tube as in step 2 above.

2.  Open test cock 3. Installing EZ-TC adaptor fitting opens test 

cock 3.

3.  Open test cock 4. EZ-TC on test cock 4 would already be 

open. The water should maintain its position in the sight tube. 

A.  If it slowly drops and simultaneously runs out through test 

cock No. 3, check valve No. 2 is leaking and must be 

serviced.

  B.  If it slowly drops and does not run out through test cock 

No. 3, then No. 2 ball valve has a small leak, but No. 2 

check valve is tight.

  C.  If it does not drop, but there is slow leakage at test cock 

No. 3, then No. 1 ball valve has a small leak, but No. 2 

check valve is tight.

Open

Closed

Dust 

Cover

Hose

EZ-TC Test Cock

IS-TK-7   1322 

EDP# 1910207 

© 2013 Watts

USA:

 Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: 

Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca 

Limited Warranty:

 Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of 

original shipment.  In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.  

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.  THE COMPANY MAKES NO OTHER 

WARRANTIES, EXPRESS OR IMPLIED.  THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED 

WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special 

or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting 

from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no 

control.  This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.  

Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages.  Therefore the above 

limitations may not apply to you.  This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State.  You should consult applicable state laws to 

determine your rights.  

SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF 

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

A Watts Water Technologies Company

WARNING:

 This product contains chemicals known to the 

State of California to cause cancer and birth defects or 

other reproductive harm.

For more information: www.watts.com/prop65

Отзывы: