Weil-McLain Evergreen

Raypak XFyre and XPakFT

Viessmann Vitodens 100-W, WB1B

Viessmann Vitodens 200-W, B2HP 
and Vitocrossal 300 CU3A

•  Set boiler PIM DIP switch 2 to Down.
•  Set boiler PIM DIP switch 5 to Up.

•  Use Local Priority 1 for DHW tank heating.
•  Use Local Priority 2 for the RoomResponse

TM

 signal.

•  Set Local Priority 2 Supply Min to 60°F.
•  Set Local Priority 2 Supply Max to 180°F.
•  Set Local Priority 2 Volts For Min to 2 V.
•  Set Local Priority 2 Volts For Max to 10 V.

•  Install the OpenTherm Module as per the boiler 

manufacturer's instructions.

Raypak XFyre or XPakFT

302P

J2

J1

+

X

X

+

T

T

8 9

9 10

Viessmann 

OpenTherm Module

Viessmann 

Extension Module EA1 

Plug 0-10V

Weil-McLain 

Evergreen P15

302P

302P

302P

+

1

4

+

+

1

2

+

+

5

+

6

•  Connect to the Viessmann Extension Module EA1 

Plug 0-10V.

Switching Relay 302P 

Two Zones with Priority

Literature

Submittal 302P_C, Installation Manual 302P_D, Job Record 302P_J

Packaged weight

5.0 lb. (2250 g)

Dimensions

8-3/16” H x 10-11/16” W x 2-3/8” D (208 x 271 x 60 mm)

Enclosure

Cover: ABS plastic, Base: galvanized steel, NEMA type 1

Approvals

CSA C US, RoHS

Ambient conditions

Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing

Power supply

115 V (ac) ±10%, 60 Hz, 11 A

Transformer

40 VA at 24 V (ac), expandable to 80 VA with additional transformer M3069 (sold 
separately)

Fuses

T5A 250 V slow blow 5 x 20 mm glass fuse, two spare fuses included

Control load

7 VA at 24 V (ac)

Pump relays

115 V (ac), 5 A, 1/3 hp, 10 A combined

Boiler XX end switch

24 V (ac), 5 A

DHW end switch

24 V (ac), 5 A

Mod boiler output

0-10 V (dc) 500 Ω min load impedance / 4-20 mA 1 kΩ max load impedance

Technical Data

Содержание Tekmar Switching Relay 302P Series

Страница 1: ...ing to a zoned hydronic heating system RoomResponseTM signal Compatible with all low voltage thermostats Unlimited zone expansion Zone priority Priority override Pump exercising Post purge Away signal...

Страница 2: ...if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all...

Страница 3: ...crewdriver Needle nose pliers Wire stripper 18 AWG LVT solid wire low voltage connections 14 AWG solid wire line voltage connections Four 1 8 1 wood screws 1 Switching Relay 302P 2 Spare fuses located...

Страница 4: ...able Away C R Rh W R W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0 10...

Страница 5: ...t required Away C R Rh W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0...

Страница 6: ...0V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L N...

Страница 7: ...Switching Relay set to Master When using multiple Switching Relays and or Zone Valve Controls set one control to Master and set all other controls to Member The boiler end switch XX only closes when t...

Страница 8: ...Master Mod Max Max Voltage Max mA 50 5 12 60 6 13 6 70 7 15 2 80 8 16 8 90 9 18 4 100 10 20 FUSE 6 70 80 90 60 50 100 MOD MAX Mod Max dial set to 100 in the illustration Boiler Make Model Required Ad...

Страница 9: ...Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1...

Страница 10: ...tpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 302P 302P 302P 302P 302...

Страница 11: ...P 302P 302P 1 4 1 2 5 6 Connect to the Viessmann Extension Module EA1 Plug 0 10V Switching Relay 302P Two Zones with Priority Literature Submittal 302P_C Installation Manual 302P_D Job Record 302P_J P...

Страница 12: ...made by Pur chaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indemnify and hold tekma...

Отзывы: