5
Step 1 - Rough In Wiring
• Pull three conductor 18 AWG LVT cable, up to 500 feet (150 m) for the float-
ing action signal.
• Strip wire to 3/8" (10 mm) for all terminal connections.
Step 2 - Mounting
• Using a Phillips screwdriver, remove the two screws in the corners of the
actuator cover. Remove the cover.
• Thread the anti-rotation bolt into one of the threaded holes on the mixing
valve. Do not align the anti-rotation bolt with the actuator motor corner cavity.
• Install coupler onto mixing valve stem, ensuring that it is pushed all the way
on.
• Black coupler: for 3-way valves 710, 711, 712, 713, 714
• White coupler: for 4-way valves 720, 721, 722, 723, 724
• Install actuator body onto the coupler.
10
0
0
.2
.4
.6
.8
1
Screw
Handle
Scale
Plate
Actuator
Motor
Anti-Rotation
Bolt
Coupler
Mixing
Valve
Mixing Valve
Stem
Corner Cavity