Parameter
Range
Description
FIXED LEAD
Off or On
Default: Off
Select if boiler 1 is always the first boiler to fire . This feature is useful in cases whereby
boiler 1 primes the flue gas venting .
FIXED LEAD TYPE
First On/First Off or
First On/Last Off
Default: First On/Last
Off
Select if boiler 1 is the first on/first off or first on/last off . Available when Fixed Lead
is On .
FIXED LAST
Off or On
Default: Off
Select if the last available boiler is always the last to fire . When using a 294 the last
boiler is 4 . If there is one 294EXP expansion then the last boiler is 8 . If there are two
294EXP expansions then the last boiler is 12 . If there are three 294EXP expansions
then the last boiler is 16 .
COMBUSTION AIR
DELAY
0 to 360 seconds
Default: 0 seconds
Set the time that the combustion air damper is open before turning on the first boiler .
VARIABLE PRIMARY
FLOW
Boiler pumps or
Isolation valves
Default: Off
Select if the boilers each have a boiler pump or if there is a variable speed system
pump with isolation valves per boiler .
OUTDOOR SENSOR
Control, tekmarNet,
Internet
Default: Off
Set the source of the outdoor air sensor reading . tekmarNet is available when
connected to a tekmarNet communication system . Internet is available when
connected to the Internet through Ethernet or Wi-Fi .
PRESSURE SENSOR
Off or On
Default: Off
Select if a pressure sensor is installed .
EXERCISING
Off or On
Default: Off
Select if the control should exercise the pumps and valves every 72 hours to prevent
seizure .
BOILER MODBUS
Off or On
Default: Off
Select if the control is connected to the boilers using Modbus communication .
ALERTS
HIGH BOILER
TEMPERATURE
ALERT
50 to 230°F
(10 .0 to 110 .0°C)
Default: 230°F (110 .0°C)
Set the threshold above which the control triggers a high temperature alert notification .
LOW BOILER
TEMPERATURE
ALERT
50 to 230°F
(10 .0 to 110 .0°C)
Default: 50°F (10 .0°C)
Set the threshold below which the control triggers a low temperature alert notification .
BOILER PLANT NO
HEAT ALERT
0 .5 to 80 .0 minutes
Default: 10 .0 minutes
Set the amount of time of no temperature change while boilers are firing after which
the control triggers a boiler plant no heat alert notification .
HIGH PRESSURE
ALERT
0 to 150 psi
(0 to 1050 kPa)
Default: 50 psi (1050
kPa)
Set the threshold above which the control triggers a high pressure alert notification .
LOW PRESSURE
ALERT
0 to 150 psi
(0 to 1050 kPa)
Default: 0 psi (0 kPa)
Set the threshold below which the control triggers a low pressure alert notification .
Settings (6 of 8)