
22
IOM-T-294
2205
© 2022 tekmar
Parameter
Range
Description
HEATING CALLS > CENTRAL HEATING
CENTRAL HEATING
Off or On
Default: Off
Select if the control responds to central heating calls . When connected to a
tekmarNet system, this setting is forced on and not visible .
ROOM
OCCUPIED
35 to 100°F
(2 .0 to 38 .0°C)
Default: 70°F (21 .0°C)
Set the desired room air temperature during the occupied periods .
ROOM
UNOCCUPIED
35 to 100°F
(2 .0 to 38 .0°C)
Default: 65°F (18 .5°C)
Set the desired room air temperature during the unoccupied periods .
This item is only available when Schedule > Device Schedule is On .
TERMINAL UNIT
Radiant Floor,
Baseboard, Radiator,
Fan Coil
Default: Baseboard
Set the type of terminal units that are being used for the space heating system .
BOILER START
TEMPERATURE
35 to 100°F
(2 .0 to 38 .0°C)
Default: 70°F (21 .0°C)
Set the starting boiler water temperature for the heating curve .
OUTDOOR START
TEMPERATURE
35 to 100°F
(2 .0 to 38 .0°C)
Default: 70°F (21 .0°C)
Set the starting outdoor temperature for the heating curve .
OUTDOOR DESIGN
TEMPERATURE
-60 to 45°F
(-51 .0 to 7 .0°C)
Default: 10°F (-12 .0°C)
Set the coldest outdoor air temperature for the heating curve for the coldest day
of the year .
BOILER DESIGN
TEMPERATURE
50 to 230°F
(10 .0 to 110 .0°C)
Default: 180°F (82 .0°C)
Set the boiler supply water temperature for the heating curve on the typical coldest
day of the year .
WARM WEATHER
SHUT DOWN
Off or On
Default: Off
Select if the control should shut down the central heating based on the outdoor
air temperature .
WARM WEATHER
SHUT DOWN
OCCUPIED
35 to 100°F
(2 .0 to 38 .0°C)
Default: 70°F (15 .5°C)
Set the outdoor air temperature at which the central heating is shut off during the
occupied period .
WARM WEATHER
SHUT DOWN
UNOCCUPIED
35 to 100°F
(2 .0 to 38 .0°C)
Default: 60°F (21 .0°C)
Set the outdoor air temperature at which the central heating is shut off during the
unoccupied period .
HEATING CALLS > DOMESTIC HOT WATER
DHW
Off or On
Default: On
Select if the control responds to domestic hot water heating calls .
DHW TYPE
System, Side Arm,
Dedicated
Default: System
Set the type of DHW heating . System refers to the DHW tank being located on
the system loop . Side Arm refers to the DHW tank being located on boiler 1 on
the near boiler piping . Dedicated refers to a system with only DHW heating loads .
DHW SENSOR
Off or On
Default: Off
Select if a sensor measures the DHW tank temperature for configurations where
DHW Type is System . The DHW Sensor is mandatory in Side Arm and Dedicated
applications .
DHW TANK
OCCUPIED
50 to 230°F
(10 .0 to 110 .0°C)
Default: 140°F (60 .0°C)
Set the DHW tank temperature during the occupied period . Available when a DHW
Sensor is set On .
Settings (2 of 8)