IOM-T-294
2205
© 2022 tekmar
23
Parameter
Range
Description
DHW TANK
UNOCCUPIED
50 to 230°F
(10 .0 to 110 .0°C)
Default: 130°F (54 .5°C)
Set the DHW tank temperature during the unoccupied period . Available when DHW
Sensor is set On .
DHW TANK
DIFFERENTIAL
1 to 42°F
(0 .5 to 23 .5°C)
Default: 6°F (3 .5°C)
Set the DHW tank differential . The DHW call turns on when the temperature reaches
the DHW Tank Occupied/Unoccupied setpoint minus the DHW Tank Differential .
Available when DHW Sensor is set On .
DHW EXCHANGE
OCCUPIED
50 to 230°F
(10 .0 to 110 .0°C)
Default: 180°F (82 .0°C)
Set the boiler water heat exchanger temperature to heat the indirect DHW tank
during the occupied period . Available when DHW Sensor is set Off .
DHW EXCHANGE
UNOCCUPIED
Off or On
Default: Off
Select if the DHW tank is heated during the unoccupied period . Available when
DHW Sensor is set Off .
INDIRECT DHW
PRIORITY
Off or On
Default: Off
Select if the indirect DHW tank has priority over the central heating load .
INDIRECT
DHW PRIORITY
OVERRIDE
20 to 240 minutes
Default: 240 minutes
Set the DHW priority override time after which central heating is resumed . Available
when Indirect DHW Priority is On .
INDIRECT DHW
SYSTEM PUMP
Off or On
Default: Off
Select if the system pump should operate during an indirect DHW call . Available
when DHW Type is System .
INDIRECT DHW
BOILER LIMITING
1 to 16
Default: 2
Set the maximum number of boilers to respond to a DHW call . The limit does not
apply when there are simultaneous central heating or setpoint calls .
HEATING CALLS > CONSTANT SETPOINT
CONSTANT
SETPOINT
Off or On
Default: Off
Select if there are constant setpoint heating loads .
CONSTANT
SETPOINT
OCCUPIED
50 to 230°F
(10 .0 to 110 .0°C)
Default: 180°F (82 .0°C)
Set the constant setpoint during the occupied period . Available when Constant
Setpoint is On .
CONSTANT
SETPOINT
UNOCCUPIED
Off or On
Default: Off
Select if the Constant Setpoint call is heated during the unoccupied period .
CONSTANT
SETPOINT
SYSTEM PUMP
Off or On
Default: Off
Select if the system pump should operate during a Constant Setpoint call .
HEATING CALLS > REMOTE SETPOINT
REMOTE SETPOINT
Off or On
Default: Off
Select if there are remote setpoint heating loads . Note: When set on, the outdoor
air sensor input changes to measure an EMS analog signal input .
INPUT EMS SIGNAL
0-10 or 2-10
Default: 0-10
Set the EMS analog signal range . Available when Remote Setpoint is On .
INPUT EMS OFFSET
-10 to 10°F
(-5 .5 to -5 .5°C)
Default: 0°F (0 .0°C)
Set the offset from the boiler target temperature interpreted from the EMS analog
input signal . Available when Remote Setpoint is On .
BOILERS 1 TO 16
BOILER AVAILABLE
Off or On
Default: Off
Select if the boiler is available as part of the firing sequence . The boiler should be
set Off if not in use or the boiler is off line for maintenance .
Settings (3 of 8)