Fitting

NVFN Series

Liquid and gas fuel shut-off valve FLAMSTOP 

NVFN Series

 – WATTS brand. Positive action with manual resetting. Liquid 

expansion thermostat. Capillary length 5m. Compact sensor. Aluminium body, stainless steel springs. NBR seals (FPM on 
1/2” and 3/4” versions). 1/2”M sensor sheath connection (with 1/2”F x 3/4”M nipple). Setpoint temperature 97°C±3°C. Max. 
operating pressure: 6 bar (DN 15-25) - 1 bar (DN 32-80).  Max. temperature, sensor side 120°C. Maximum temperature, valve 
side 50°C. 1/2” and 3/4” versions suitable for biodiesel.  INAIL approved and set. Compliant with Directives PED 2014/68/EU 
and ATEX 2014/34/EU.

DN

L

H

H1

1/2”

70

155

138

3/4”

70

163

141

1”

90

196

169

1.1/4”

150

204

169

1.1/2”

150

204

169

2”

170

222

179

1/2”

H

D

H1

D

52,5

L

500

0

DN

L

H

H1

65

260 310 200

80

310 351 234

1/2”

H

D

H1

D

52,5

L

500

0

To reset the valve, proceed as follows:

A)

 Release the black protective cap;

B)

 Pull the green reset knob up;

A)

 Re-engage the black protective cap.

To make sure the valve is open, check that the green reset knob appears in the top inspection window on the protective cap.

A

C

B

To fit the 

NVFN Series

 fuel shut-off valve, proceed as follows:

1. Screw the sheath of the heat-sensitive element onto the sleeve;
2. Insert the bulb of the heat-sensitive element fully into the sheath;
3. Connect the valve to the burner supply pipe in accordance with the direction of flow shown on the valve body;
4. 

Carefully unroll the copper capillary, making sure that it is not resting on hot parts or the boiler 

 doors;
5. Push the plastic protective bushing on the end of the capillary into the sheath, then tighten the screw on the hexagonal 

head of the sheath.

N.B.

 You can turn the control device on the cap through 360° to make it easier to fit the valve and lay out the capillary.

Specification text

Overall dimensions (mm)

Resetting the valve