background image

3

Watts Water Technologies, Inc.

Operation

Installation

Chart

1000

500

200

100

10

20

50

100

200

500

1.000

2.000

5.000

10.000

20.000

50.000

DN32

DN25

DN15

PRESSURE DROP

100

200

500

1000

2000

5000

10000

50000

3

5

10

20

50

100

200

500

1000

DN20

DN40

DN50

DN65

DN80

FLOW RATE

[

 mm c.a.

]

Q (kg/h) - Gasolio

Q (kg/h) - Olio combustibile

(3÷5 °E)

Q (Nm

3

/h) - Metano

      (d=0,583)

When the setpoint temperature is reached, the heat-sensitive element 

(4)

 causes the grooved piston supporting the stem with 

integral disc 

(2)

 to move, causing the stem to drop, thus closing the valve. Valve closing is not gradual: the valve snaps shut 

when the setpoint temperature is reached, so the fuel flow is not throttled. It is not possible to reset the valve until the water 
temperature has fallen below 85°C.

1

2

3

5

6

4

Characteristics

1) Resetknob
2) Disc
3) Cover
4) Heat-sensitive element
5) Valve body
6) Sheath

Install the fuel shut-off valve on the fuel supply pipe between the filter and the burner, in the direction shown by the arrow cast 
into the valve body. The valve's heat-sensitive element “must be immersed in the outward flow of hot water, close to or at the 
top of the boiler, or in the outlet pipe within 1m of the boiler, upstream of any shut-off device” (R.2.A.4.2) 

(Fig.1)

. Weld the sheath 

sleeve so that the sheath is immersed as fully as possible in the hot water, in one of the positions specified above. Depending 
on the diameter of the pipe, the sleeve can be welded perpendicular or at an inclined angle in relation to the pipe 

(Fig.2)

 or on 

a bend where possible 

(Fig.3)

.

Fig.2

Fig.1

Flow rate - pressure drop

Fig.3

Отзывы: