4 - Maintenance:

4-1 Maintenance

4-1-1 Checking the element:

If the flow is reduced or if the temperature fluctuates, check the 
condition of the element. If necessary, clean and descale the 
element with weak diluted acid. 
Clean the filters. If this does not work, replace it (4-2).

4-1-2 Draining in the event of freezing:

When the appliance is exposed to frost, it is essential to empty 
it and remove the element, taking off the element. Once the ins-
tallation is emptied, put the element back place after lubricating 
it with a silicon grease.

4-2 Replacing the mechanism

Close the hot and cold water inlet stopcocks, then turn the taps 
on and off to lower the pressure inside the appliance.
Proceed as indicated in the INSTALLATION part starting from 
1-2 Rinsing.
Make sure the mechanism is correctly fitted in the box.

Disinfecting procedure for fighting against legionnaire’s  
disease,

2 possible methods:

-  Thermal flash:

 

Run hot water through the mixer tap (bacteria is eliminated from 
60°C).
Remove the cap (W) after having removed the screw, then turn 
the adjustment ring (Y), to the full hot position, the mixer will 
deliver very hot water.

-  Using the rinsing kit:

 

Flush using a disinfectant solution or with very hot water (hotter 
than 90°C) without risking damage to the appliance.

-  Unscrew the screw and remove the cap (W), unscrew the nut 

(X), remove the cartridge (Z) then insert the rinsing kit (V) and 
re-tighten the nut (X)

- Re-open the hot water stopcock.
-  Turn on the tap(s) to circulate the hot water and carry out a 

proper thermal disinfection.

Warning:  

always comply with local regulations concerning 
disinfecting procedures, such as wearing suitable 
masks and gloves, etc.

Содержание MINIMIXing

Страница 1: ...MINIMIXing Thermostatic mixing valve for point of use Installation and Operation Manual wattswater eu ...

Страница 2: ...u tournant UK Swivel nut IT Dado girevole NL Vrouwelijke moer DE Überwurfmutter G 3 8 ISO228 ES Tuerca giratoria RU Накидная гайка PL Nakrętka obrotowa DK Drejemøtrik 5 6 7 93 8 71 7 31 G 1 2 B ISO228 G 1 2 B ISO228 G 1 2 B ISO228 Ø42 Ø42 Ø15 FR Raccord compression UK Compression fitting IT Collegamento a compressione NL Knelkoppeling DE Klemmkupplung ES Conexión de compresión RU Компрессионный фи...

Страница 3: ...W X Z U Y B1 B2 B3 Y Y Y Y X V 3 MM IM FR W UK 06 18 Rev 0 0 5 10 15 20 25 30 0 5 0 1 1 5 2 2 5 3 5 3 Débit L min Perte de charge bar Flow curve Flow rate Head loss P bar L min ...

Страница 4: ...and re tighten the nut X Supply hot and cold water rinse the piping by letting the water flow abundantly Turn off the hot and cold water then unscrew the nut X and remove the rinsing kit V refit the cartridge Z and re tighten the nut X 1 3 Adjusting the temperature factory set to 38 C diagram B2 page 3 Turn on the water supply to the appliance Calibrate the temperature Run the water at the require...

Страница 5: ... When the appliance is exposed to frost it is essential to empty it and remove the element taking off the element Once the ins tallation is emptied put the element back place after lubricating it with a silicon grease 4 2 Replacing the mechanism Close the hot and cold water inlet stopcocks then turn the taps on and off to lower the pressure inside the appliance Proceed as indicated in the INSTALLA...