Aegis Sequencer
Setup
L-OMM-015_0B
• 8/8/2023 Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
7
of
38
V.
Ensure the Slave ID # is matches the number of the unit (example: Unit 3 has Slave ID 3).
VI.
Repeat these steps until all units have their matching IP addresses in the Slave
Parameters.
7. Disable Temperature Probes BT1 and BT2 for each unit. These settings are accessed through the
remote interface of each unit.
I.
Using a browser, enter the IP address of a unit into the address bar. For more
information on the remote interface, reference L-OMM-013.
II.
Select User Setting.
III.
Set temperature probes BT1 and BT2 to DISABLED.
If individual unit heat exchanger modules and primary pumps are being used, these pumps must
be ENABLED in the Service menu.
If a single external heat exchanger and primary pump is being used, the individual unit primary
pumps must be DISABLED in the Service menu.
Please note:
This is not a recommended application, as the Lync heat exchanger modules are
only designed to work with a single heat pump. Note that this is not a recommended
application.
8. Ensure that there are no errors or alarms displayed. Hold the alarm button down for three
seconds to reset all alarms. Press the alarm button to check for the status of the alarms. If none
are present the alarm screen will appear as follows: