Problem & Cause

Answer

A. Fluctuating or erratic hot water temperature at fixture. 

A.1  Heavy draws of either cold or hot water elsewhere in 

the system, such as clothes washer or dishwasher.

A.1  See warning on reverse side. Hot water temperature control valves cannot compensate 

for this condition. Check valves in hot and cold legs to hot water temperature control valve 

would help but not cure the problem. 

A.2 Unbalanced pressures.

A.2  Install balancing or throttling valves (shutoff valves) in hot and cold legs to hot water 

extender tempering valve and adjust accordingly for demand. 

B. Hot water backing up into cold water line.

B.  Hot water pressure overriding cold pressure.

B. Install check valve in cold water leg to hot water temperature control valve.

C. Cannot adjust water temperature to desired temperature.

C.1 Unequal pressures.

C.1  A balancing or throttling valve must be installed in the cold water leg to the hot water 

temperature control valve to throttle or restrict the pressure. In most installations, the cold 

water supply line feeds both the hot water temperature control valve and the water heater 

or tankless heater. To compensate for the pressure drop through the heater, the cold 

water to the hot water temperature control valve must be throttled or reduced. 

C.2 Hot or cold temperature differential.

C.2  Check water heater controls to verify that the water temperature is the same as the 

heater thermostat setting. 

C.3 Valve undersized.

C.3  Check gpm flow required versus gpm flow capacity of valve. 

D. High pressure drop through hot water temperature control valve. 

D. Valve undersized.

D. Install larger hot water temperature control valve. 

E. Insufficient hot water during peak demand 

E.1 Valve undersized.

E.1  Check gpm flow required during peak demand period and size hot water temperature 

control valve accordingly. 

E.2 Heater or capacity insufficient for demand.

F. Frequent failure of thermostatic element. 

F.1  Thermostatic element exposed to extremely high 

temperature.

F.1 Check heater thermostat setting. 
F.1a   Hot water temperature control valve must be trapped at least 8” to 12” as per installa-

tion instructions. Install check valves as recommended. 

F.2  Corrosive water conditions. (Buildup of mineral 

deposits)

F.2  Frequent cleaning of thermostat element and plunger would tend to prolong the life of 

the element. A small coating of FDA approved silicone lubricant in the piston area of the 

element would also help.

F.3 Electrolysis (pitting deterioration, etc.)

F.3 Electrically ground the piping system or install dielectric unions. 

G. All hot or cold water flows at hot fixture. 

G.1  This problem will require considerable trouble-

shooting. 

G.1 Verify that complete installation instructions were followed: 
       A. Is valve properly trapped?  

2. Check to see if thermostatic element has failed.  

3. Check to see if temperature control on water heater is set at desired  

    temperature.  

4.  Check to see if minimum flow requirements for valve size are met. Minimum flow 

requirements for LF70A series valves is 2 gpm. 

Series LF70A Troubleshooting Guide

NOTICE

After installation please leave this instruction sheet for  

occupant’s information.

 

Limited Warranty:

 Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of 

original shipment.  In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.  

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.  THE COMPANY MAKES NO OTHER 

WARRANTIES, EXPRESS OR IMPLIED.  THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED 

WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special 

or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting 

from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no 

control.  This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.  

Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages.  Therefore the above 

limitations may not apply to you.  This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State.  You should consult applicable state laws to 

determine your rights.  

SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF 

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

WARNING:

 This product contains chemicals known 

to the State of California to cause cancer and birth 

defects or other reproductive harm.

For more information: www.watts.com/prop65

IS-70A   1548 

EDP# 1910210 

© 2015 Watts

USA:

  Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com

Canada:  

Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca

Latin America:  

Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com

A Watts Water Technologies Company

Отзывы: