Installation, Maintenance, and Repair Manual

 

Series LF007 Model IOT

Double Check Valve Assemblies

21/2" – 3"

NOTICE

For Australia and New Zealand, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow 

preventer.
Watts

®

 product specifications in U.S. customary units and metric 

are approximate and are provided for reference only. For precise 

measurements, contact Watts Technical Service. Watts reserves 

the right to change or modify product design, construction, spec-

ifications, or materials without prior notice and without incurring 

any obligation to make such changes and modifications on Watts 

products previously or subsequently sold.

RP/IS-LF007-IOT

Testing

For field testing procedure, refer to the Watts installation sheets  

IS-TK-DL, IS-TK-9A, IS-TK-99E, and IS-TK-99D at  

www.watts.com.
For other repair kits and service parts, refer to the Backflow 

Prevention Products Repair Kits & Service Parts price list  

PL-RP-BPD at www.watts.com.
For technical assistance, contact your local Watts representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Local building or plumbing codes may require modifications 

to the information provided. You are required to consult 

the local building and plumbing codes prior to installation. 

If the information provided here is not consistent with  

local building or plumbing codes, the local codes should 

be followed. This product must be installed by a licensed 

contractor in accordance with local codes and ordinances.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product 

must be tested periodically in compliance with local codes, but 

at least once per year or more as service conditions warrant. 

All products must be retested once maintenance has been 

performed. Corrosive water conditions and/or unauthorized 

adjustments or repair could render the product ineffective for 

the service intended. Regular checking and cleaning of the 

product’s internal and external components helps assure  

maximum life and proper product function. 

WARNING

!

Series LF007 is designed for installation at referenced cross-

connections to prevent the backflow of polluted water into the 

potable water supply. Model IOT (available only with NRS gate 

valves) includes factory-installed pressure sensors on three test 

cocks (No. 2, No. 3, and No. 4).

LF007-NRS-IOT

NOTICE

Use of integrated pressure sensors on and monitoring connection 

kit with IOT models does not remove the need to comply with all 

required instructions, codes, and regulations related to installation, 

operation, and maintenance of the backflow preventer.
Watts is not responsible for data transmission failures due to 

power issues.

NOTICE

For IOT models, an add-on monitoring connection kit is required 

to collect psi measurements from the integrated pressure sen-

sors. Without the connection kit, the pressure sensors are passive 

components and will not communicate with any other device. 

For BMS only. (The connection kit and pressure sensors are 

also available for existing installations. See “Add-on Monitoring 

Connection Kits,” for ordering details.)

Содержание LF007 IOT Series

Страница 1: ...or plumbing codes the local codes should be followed This product must be installed by a licensed contractor in accordance with local codes and ordinances WARNING Need for Periodic Inspection Mainten...

Страница 2: ...ons Outside Building Above Ground In an area where freezing conditions do not occur Series LF007 can be installed outside of a building See Figure 2 The most satisfactory installation is above ground...

Страница 3: ...as necessary For more information refer to repair parts price list PL RP BPD 5 Reassemble the check valve modules Check modules are installed in the valve body with the seats facing the valve inlet T...

Страница 4: ...irst paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and the Company shall not be responsible for any incidental special or consequential damages inclu...

Страница 5: ...e plomberie locaux les codes locaux pr valent Ce produit doit tre install par un entrepreneur autoris et respecter les codes et les ordonnances locaux AVERTISSEMENT Besoin d une inspection d une maint...

Страница 6: ...a pas de conditions de gel la s rie LF007 peut tre install e l ext rieur d un b timent Voir la figure 2 L installation la plus satisfaisante est au dessus du sol et doit tre r alis e de cette mani re...

Страница 7: ...ur plus d informations reportez vous la liste de prix des pi ces de r paration PL RP BPD 5 Remonter les modules de clapet antiretour Les modules de clapet sont install s dans le corps de vanne les si...

Страница 8: ...pour transmettre les mesures de pression de l ensemble de la vanne un syst me de gestion du b timent consiste en un module d interface avec trois 3 c bles de capteur un c ble de donn es et un adaptat...

Страница 9: ..._________________________________________________________________________________________________________ ______________________________________________________________________________________________...

Страница 10: ...roduit ne fonctionne pas correctement autres co ts aff rents aux frais de main d uvre de retards de vandalisme de n gligence d engorgement caus s par des corps trangers de dommages caus s par des cond...

Страница 11: ...s reglamentos locales de construcci n o plomer a se deben seguir los reglamentos locales Este producto debe ser instalado por un contratista autorizado de acuerdo con los reglamentos y ordenanzas loca...

Страница 12: ...arse en el exterior de un edificio Consulte la figura 2 La instalaci n m s satisfactoria se realiza sobre el suelo y debe instalarse de esta manera siempre que sea posible En un rea donde se pueden pr...

Страница 13: ...aci n consulte la lista de precios de las piezas de reparaci n PL RP BPD 5 Vuelva a montar los m dulos de la v lvula de retenci n Compruebe que los m dulos est n instalados en el cuerpo de la v lvula...

Страница 14: ...para transmitir mediciones de presi n del conjunto de v lvula a un sistema de gesti n de edificios consta de un m dulo de interfaz con tres 3 cables de sensor cable de datos y adaptador de alimentaci...

Страница 15: ...________________________________________________________________________________________________________ _______________________________________________________________________________________________...

Страница 16: ...funciona correctamente otros costos resultantes de cargos laborales retrasos vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu...

Отзывы: