6
IOM-WQ-BB-S100
2127
EDP# 68110146
© 2021 Watts
Equipment Specifi cations
SYSTEM MODEL NO. BB-S100
Minimum/Maximum Operating Temperature*
34 to 125°F / 1 to 52°C (125°F / 52°C at 80psi Maximum Pressure)
Minimum/Maximum Operating Pressure*
25psi to 125psi / 172 kPa to 861 kPa
Maximum Continuous Flow Rate for Lead & PFAS Reduction**
4 GPM (15 lpm)
Maximum Flow Rate for Chlorine Reduction***
13 GPM (49.2. lpm)
Maximum Flow Rate for Chloramine Reduction***
7 GPM (26.4 lpm)
Inlet and Outlet Connection Size/Type
1" NPT
Unfiltered Water Housing Drain Port Connection Size/Type
½" FNPT
Filter Housing Body Material
Glass Reinforced Polypropylene
Inlet Pressure Gauge Port
1⁄4" FNPT Brass Reinforced
Inlet Pressure Gauge Included
Yes
Swing Bolts (Lid) Material
304 Stainless Steel
O-ring (Lid) Material
EPDM
O-ring (Plumbing Adaptors) Material
EPDM
Nominal Micron Rating
0.5 Micron Nominal
Filter Housing Anchor Kit Included
Yes- 3/8" Concrete Anchors (X3)
Number of Filter Cartridges
1
Filter Cartridge Media Type
Lead Adsorption Carbon Block
Filter Cartridge End Cap Material/Color
Glass Reinforced Polypropylene/Green
Filter Cartridge Top Endcap Includes Handle
Yes
Filter Cartridge O-ring (Dual) Material
EPDM
Maximum Allowable Filter Cartridge Pressure Drop
40psi Drop
Flow Monitor Display Type
5 Digit LCD- Volumetric Count Down to “0”
Flow Monitor Capacity
84,480 Gallons (Resettable / Non Programmable)
Positive Indication of Flow
Yes- Flow Wave Icon On Display
Flow Monitor Alarm at “0” Gallons Remaining
During Water Flow: Visual- Flashing “0 gal” on Display/ Audible- Beeping Alarm
Flow Monitor Power Supply
2 AA Alkaline Batteries
Low Battery Alarm
Yes- Visual Low Battery Icon and Audible Beeping Alarm
Flow Meter Type
Inline Flow Through Turbine Meter
Flow Meter Connection Size/Type
1" x 1" MNPT
Flow Meter Body Material
Glass Reinforced Polymer
* Minimum and Maximum Operating Temperatures and Pressures listed above apply to complete system as well as all individual components including
filter housing, filter cartridge and volumetric flow monitor/meter.
** See Certified Substance Reduction for specific flow and reduction claims.
*** Claims are not performance tested or certified by IAPMO. Performance claims are based on independent laboratory and manufacturer’s internal test
data. Actual performance is dependent on influent water quality, flow rates, system design and application. Results may vary. See Certified Substance
Reduction for certified chlorine flow and reduction claims.
Flow Rate and Pressure Drop
Low Pressure Drop
The Watts BB-S100 system uses
a large, high capacity carbon block
filter cartridge to ensure the highest
degree of performance while offer-
ing the highest possible flow rate at
the lowest possible pressure drop.
Pressure drop testing conducted
at Watts’ Peoria, AZ facility using
approximately 73ºF water. Test
results reflect new filter cartridge
flow rate and pressure drop perfor-
mance.
0
5
10
15
20
25
30
1
2
3
4
5
6
7
8
9
10
11
12
Pressure Drop (psi)
Flow Rate (GPM)
Flow Rate and Pressure Drop