Benchmark 750-3000 Boiler Installation & Startup Manual
SECTION 6 – BOILER SEQUENCING TECHNOLOGY
OMM-0121_D
•
GF-205
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 104 of 122
OPTION 3 - Outdoor Reset With Direct Wired Header Sensor And Direct
Wired Outdoor Sensor Instructions
Step 3 - Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration
menu and set the BST Menu item to
Enabled
.
2. Go to the Boiler Sequencing Menu and set the BST Mode item to
BST Client
(for now).
On MANAGER only:
3. Go to the BST Setpoint item and enter the Failsafe Setpoint.
4. Go to the BST Setup Menu item and set to
Enabled
.
5. Go to the BST Setpoint Mode item and select
Outdoor Reset
.
6. Go to the Head Temp Source item and select
FFWD Temp
.
7. Go to the BST Outdoor Sens item and select
Enabled
.
8. Go to the Outdoor Temp Source item and select
Outdoor Temp
.
When ALL C-More units have been configured:
9. Go to the Boiler Sequencing Menu of the Manager unit and set the BST Mode item to
BST
MANAGER
.