background image

16

IOM-A-Deringer 40/40X/50/50X_6-8

 

   2005 

EDP#2916006

 

© 2020 Watts

Limited Warranty: 

Ames Fire & Waterworks (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date 

of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.

THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER 

WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE 

IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special 

or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from 

labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control.  

This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.

Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the 

above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to 

determine your rights. 

SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES 

OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

USA: Backflow

  T: (978) 689-6066 • F: (978) 975-8350 • AmesFireWater.com

USA: Control Valves

  T: (713) 943-0688 • F: (713) 944-9445 • AmesFireWater.com

Canada:

  T: (888) 208-8927 • F: (888) 479-2887 • AmesFireWater.ca

Latin America:

  T: (55) 4122-0138 • AmesFireWater.com

Step 1:  Using wire cutters, cut the wires coming out of the  

gearbox as close to the gearbox as possible. 

Step 2:  Use a piece of thread seal tape to seal the threads on a 

½" NPT plug 

Step 3:  Using an allen wrench, install and tighten the ½" NPT 

plug into the same threaded hole where the wires were 

previously cut. 

NOTICE

If a Deringer is going to be installed outdoors and the tamper switches will not 
be wired into the fire alarm system, the wires will need to be cut and a plug 
will need to be installed to protect the internal components of the gearbox.   

Содержание AMES Deringer 40

Страница 1: ...and follow all safety and use information can result in death serious personal injury property damage or damage to the equipment Keep this manual for future reference You are required to consult the l...

Страница 2: ...ool can be used For example allen wrenches instead of allen drive sockets Tools Required 15 16 Socket 11 8 Socket Wood Block 2 x 4 x 5 Wood Block 1 x 2 x 16 2 Phillips Head Screwdriver 2 Flathead Scre...

Страница 3: ...cks water will be released Take precautions to ensure discharging water does not damage the surrounding area equipment or create an unsafe condition 1 DO NOT OPEN Main test cock number 1 as it is stil...

Страница 4: ...til the ends of the bolts are flush with the inner wall of the valve body B 2 Insert a flathead screwdriver between the inner valve body and the first check module flange C gently push the first check...

Страница 5: ...damage or fouling to the sealing seat Do not remove unless the seat cage is being replaced 6 Reverse the order of above instructions to reassemble bypass check valve A Part 2 1 To replace a damaged r...

Страница 6: ...l gaskets F before threading meter coupling nuts into place B C E E G F E FLOW D A Maintenance of First True Seal Check Module 1 Use a 2 phillips head screwdriver to remove tower screws A from the fir...

Страница 7: ...lastomer disk D When replacing elastomer disk D be certain that no air water or debris is trapped in the clapper H cavity behind the elastomer disk D 4 Reverse the order of the above instructions to r...

Страница 8: ...e backside of the second check seat ring G Using a 1 x4 piece of wood cut to 16 length H as a lever between access port wall the 2 x4 F gently move the second check module A into its fully seated posi...

Страница 9: ...k retaining screws I The first check module must be fully seated to ensure retainer screws do not bind against check towers Binding retainer screws against check towers will result in permanent damage...

Страница 10: ...D D Maintenance of Relief Valve continued B D 1 Check the rubber seal on the relief valve piston assembly A for fouling or damage by making sure the indentation of the seat in the rubber seal is pres...

Страница 11: ...B making sure the diaphragm lays flush on the bottom of the piston assembly with no wrinkles or tears in the diaphragm 2 Place the relief valve spring C back onto the relief valve assembly A and slide...

Страница 12: ...the pitot tube B at the top of the pitot tube must face directly UPSTREAM toward the 1 shutoff valve Proper orientation can be confirmed visually by removing the main line valve cover and first check...

Страница 13: ...certain that access port O ring A does not become dislodged during the process 3 Insert cover bolts D and tapered washers E flat side facing up into tapered cover holes F Tapered washers E must be pr...

Страница 14: ...screwdriver close bypass test cock number 1 and 2 B Test cock is closed when screwdriver slot on stem is perpendicular to water flow through test cock 3 Use the T handles to open bypass ball valve nu...

Страница 15: ...A counterclockwise to the open position Shutoff valve is open when yellow orange position indicator flags are parallel to the mainline water flow 2 Slowly rotate the number 2 shutoff valve operation h...

Страница 16: ...ranty shall be invalidated by any abuse misuse misapplication improper installation or improper maintenance or alteration of the product Some States do not allow limitations on how long an implied war...

Отзывы: