Modulex EXT Commercial Series
CHAPTER 8: Maintenance Schedule
OMM-0160_A
• DRAFT Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
90
of
117
PARAMETER
DESCRIPTION
ENTRY RANGE
DEFAULT
483
Maximum Differential Temperature
(Water ΔT protection)
0°F/2°F
–
90°F
(0°C/1°C-50°C)
0 = Disabled;
Units may be expressed
in R or K
54°F (30°C)
380
Programmable Sensor #1 function
- NOT
APPLICABLE.
Note: Leave at default value of 1
1
777
APS check
- NOT APPLICABLE.
Note: Leave at default value of 0
0
623
Temperature sensors
0: 10K @ 25°C, B=3977
1: 10K @ 25°C, B=3435
Note: Leave at default value of 0
0/1
0
626
Temperature sensor type
0: 10K @ 25°C, B=3977
1: 10K @ 25°C, B=3435
2: PT1000
3: minimum water flow switch
Note: Leave at default value of 0
0/1/2/3
0
805
Supply voltage
100-240V
115V
2590
Burner Capacity
10-1000kW
MLX EXT 450 2S
-1100 2S: 50kW
MLX EXT 1500 2S
-3000 2S: 112kW