Modulex EXT Commercial Series
CHAPTER 4: Installation Instructions
OMM-0160_A
• DRAFT Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
60
of
117
TABLE 4-6: EXT Pressure, CO2 and O2 Level Calibration
MODULEX EXT 1500 2S
Type of
Gas
Supply
Press.
in w.c.
[kPa]
CO
2
levels
[%]
O
2
levels
[%]
Fan
speed
Ø Mixer
injectors
Øin (mm)
Gas Consumption
Start-
output
V
max
fan
Min.
Output
Max.
Output
Min.
Output
Max.
Output
min. max.
Minimum
Maximum
[%]
FL
FH
ft
3
/hr
(m
3
/hr)
ft
3
/hr
(m
3
/hr)
IG
FU
Natural
7.0 (1.74)
9.1
9.2
4.8
4.6
31
100
0.35 (9)
80 (2.26)
1466 (41.5)
50
91
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
595 (16.84)
50
87
FOR HIGH ALTITUDE
Natural
7.0 (1.74)
9.1
9.2
4.6
4.8
31
100
0.35 (9)
80 (2.26)
1319
(37.35)
50
83
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
536 (15.17)
50
79
MODULEX EXT 2300 2S
Type of
Gas
Supply
Press.
in w.c.
[kPa]
CO
2
levels
[%]
O
2
levels
[%]
Fan
speed
Ø Mixer
injectors
Øin (mm)
Gas Consumption
Start-
output
V
max
fan
Min.
Output
Max.
Output
Min.
Output
Max.
Output
min. max.
Minimum
Maximum
[%]
FL
FH
ft
3
/hr
(m
3
/hr)
ft
3
/hr
(m
3
/hr)
IG
FU
Natural
7.0 (1.74)
9.1
9.2
4.8
4.6
31
100
0.35 (9)
80 (2.26)
2197 (62.2)
50
91
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
893 (25.3)
50
87
FOR HIGH ALTITUDE
Natural
7.0 (1.74)
9.1
9.2
4.6
4.8
31
100
0.35 (9)
80 (2.26)
1978 (56)
50
83
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
805 (22.8)
50
79
MODULEX EXT 2600 2S
Type of
Gas
Supply
Press.
in w.c.
[kPa]
CO
2
levels
[%]
O
2
levels
[%]
Fan
speed
Ø Mixer
injectors
Øin (mm)
Gas Consumption
Start-
output
V
max
fan
Min.
Output
Max.
Output
Min.
Output
Max.
Output
min. max.
Minimum
Maximum
[%]
FL
FH
ft
3
/hr
(m
3
/hr)
ft
3
/hr
(m
3
/hr)
IG
FU
Natural
7.0 (1.74)
9.1
9.2
4.8
4.6
31
100
0.35 (9)
80 (2.26)
2564 (72.6)
50
91
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
1042 (29.5)
50
87
FOR HIGH ALTITUDE
Natural
7.0 (1.74)
9.1
9.2
4.6
4.8
31
100
0.35 (9)
80 (2.26)
2306 (65.3)
50
83
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
939 (26.6)
50
79
MODULEX EXT 3000 2S
Type of
Gas
Supply
Press.
in w.c.
[kPa]
CO
2
levels
[%]
O
2
levels
[%]
Fan
speed
Ø Mixer
injectors
Øin (mm)
Gas Consumption
Start-
output
V
max
fan
Min.
Output
Max.
Output
Min.
Output
Max.
Output
min. max.
Minimum
Maximum
[%]
FL
FH
ft
3
/hr
(m
3
/hr)
ft
3
/hr
(m
3
/hr)
IG
FU
Natural
7.0 (1.74)
9.1
9.2
4.8
4.6
31
100
0.35 (9)
80 (2.26)
2931 (83)
50
91
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
1190 (33.7)
50
87
FOR HIGH ALTITUDE
Natural
7.0 (1.74)
9.1
9.2
4.6
4.8
31
100
0.35 (9)
80 (2.26)
2638 (74.7)
50
83
Propane
11.0 (2.74)
10.8
10.8
4.5
4.5
31
100
0.35 (9)
32 (0.92)
1070 (30.3)
50
79
NOTE:
Check the O
2
levels often, especially at low flow rates.