Modulex EXT Commercial Series
CHAPTER 4: Installation Instructions
OMM-0160_A
• DRAFT Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
39
of
117
4.20 Vent Starter Pieces
All vent starter pieces for the MODULEX EXT 1500 through 3060 can be purchased directly from the
vent manufacturer.
Figure 4-13: Flue Exhaust Diameter Reduction Adaptor Kit
TABLE 4-3: Vent Part Numbers
MODEL
DIA.
MATERIAL
PART NUMBER
EXT 1500 2S
10”
Stainless
Contact vent manufacturer
Polypropylene
Contact vent manufacturer
PVC
58115-1
EXT 2300 2S
–
3000 2S
12”
Stainless
Contact vent manufacturer
Polypropylene
Contact vent manufacturer
PVC
58115-2
In the case of PVC venting, the flue venting pipe is affixed to the adapter using RTV liquid silicone and
then clamped with a worm-driven Hose Clamp.
When using non-metallic (plastic) venting materials, use schedule 40 or thicker, single-wall,
uninsulated pipes. When using non-metallic (plastic) vent systems for Canadian installations, per CSA
GASKET
European-To-American
Standard Flue Adapter
DIAMETER REDUCTION ADAPTOR
CONNECTOR
WORM-DRIVEN HOSE CLAMP
WASHERS (8 EACH)
SCREWS (8 EACH)
FLUE MANIFOLD