GF-5050
Innovation Series & ReCon Water Heater
TAG-0043_0Q
Venting and Combustion Air Guide
Page
18
of
39
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
•
Phone: 800-526-0288
12/01/2016
Individually Sealed Combustion
Manifolded Sealed Combustion
Located on Different Wall From Exhaust
Located on Different Wall From Exhaust
Manifolded Sealed Combustion
Individual Sealed Combustion
Manifolded Sealed Combustion
NOTE 2
For high wind, wind blocked sites, a tee may be installed at the fresh air inlet. The leg
of the tee connects to the combustion air intake. The branches of the tee can be in the
horizontal or vertical direction, as determined by the system designer and site
conditions.
Figure 7b: Individual Vents – ACCEPTABLE Installations
IMPORTANT NOTES:
1. Please consult the AERCO factory for all applications utilizing common
ducted combustion air with common breeching of exhausts.
2. AERCO boilers and AERCO water heaters may share common combustion
air and exhaust breeching. Other configurations, not depicted in this guide,
are possible. If you intend to implement any of these options, please
contact your local AERCO representative or the AERCO factory for project
specific venting and combustion air configurations.
VENT
VENT
AIR
AIR
SEE
NOTE 2
SEE
NOTE 2
AIR
AIR
AIR
VENT
VENT
VENT