SECTION 5: INSTALLATION
– PIPING
OMM-0111_B:
•
GF-146-P
•
10/29/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 26 of 47
5.5 Safety Relief Valve
AM units come equipped with a safety relief valve on each factory installed module. Boilers are
supplied with 50 PSI pressure relief valves. If a higher or lower rated PRV is required it must be
field supplied and installed.
Pipe the discharge of the safety relief valve(s) (Figure 5-1) to a suitable drain to prevent injury in
the event of pressure relief. Each relief valve must have its own discharge piping, be piped to
within 12
” of the ground, and not be combined with any other piping all the way to the point of
discharge into a drain. Provide piping that is the same size as the safety relief valve outlet.
Figure 5-1: Discharge Piping for Boiler Relief Valves (AM 1000 Boiler Shown)
SAFETY RELIEF
VALVE & T&P GAUGE
#1
HOT WATER SUPPLY
OUTLET (Factory Connected)
FIELD INSTALLED:
RELIEF VALVE DISCHARGE
PIPING (one for each valve
and piped to within 12” of
ground)
WATER RETURN
INLET (Factory Connected)
SAFETY RELIEF
VALVE & T&P GAUGE
#3
SAFETY RELIEF
VALVE & T&P GAUGE
#2
SAFETY RELIEF
VALVE & T&P GAUGE
#4