Benchmark 3.0LN 24-Month Maintenance Kit 58015-04
Technical Instruction Document
TID-0135_0C
10
/12/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
•
Phone: 800-526-0288
Page 19 of 20
7.
FINAL REASSEMBLY AND TESTING
Upon completion of all waterside and fireside inspections, reassemble the unit and perform the
tests specified in sections 7.1 and 7.2.
7.1
Reassembly and Set-Up Following Completion of Inspections
Following completion of the all required inspections and replacements, perform the following
reassembly and setup procedures:
1. Ensure that the heat exchanger has been filled and the water supply and return valves
have been opened.
2. Turn ON the external circuit breaker to the unit.
3. At the front panel of the unit, set the
ON/OFF
switch on the C-More Control Panel to the
ON
position.
4. Press the
LOW WATER LEVEL RESET
button to reset the low water cutoff.
5. Press the
CLEAR
switch to reset the fault relay. This will turn off the
FAULT
LED and
clear any displayed error message.
6. Replace the unit side panels and top panels.
7.2
Final Testing Following Inspections
Upon completion of the inspections and replacements specified in this document, perform the
Combustion Calibration Tests specified in Chapter 4 of the O & M Manual GF-116, or GF-117
(Dual-Fuel).
Perform a water bubble test during purge to ensure the burner gaskets, replaced in section
6.1.2, are providing a good seal.
Following successful completion of the Combustion Calibration Tests, return the Benchmark
3.0LN Boiler to service use.