background image

1

Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

1/2" Orifice
Horizontal
Sidewall
Automatic
Sprinkler

Product
Description

than the recommended 2 1/4"
diameter.  The escutcheon closure
plate fits between the base of the
escutcheon and the mounting
surface.

For all models of Prohibitor

TM

sprinklers, an optional 4 1/2"
diameter x 1/8" thick security closure
plate  is  

  available for use where

additional security is a consideration.
The security closure greatly reduces
the possibility of inserting a tool,
prybar or other device behind the
sprinkler.  The security closure plate
fits between the base of the
escutcheon and the mounting
surface.

For all models of Prohibitor

TM

Sprinklers, the optional Ident-A-Fire

TM

feature is available to provide an
alarm signal upon activation of the
sprinkler.

Prohibitor

TM

 Sprinklers are

available in two standard finishes,
chrome and brass.  Their mating
escutcheon is available in three
standard finishes, chrome plated,
brass plated and white painted, with
additional special finishes available.

Operation:  A fusible alloy pellet is
compressed with a bearing disc into
a copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet.  At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from
the retaining groove.  This movement
allows system water pressure to
force the orifice sealing mechanism
and deflector assembly open. Water
is then discharged in a designed flow
pattern.

The Omega Prohibitor

TM

 Model

HEC-12 PRO Automatic Sprinklers
have been specifically designed for
use in institutional occupancies, such
as correctional facilities and mental
health facilities, where the occupants
may attempt to tamper with or
otherwise employ the sprinkler to
injure themselves or others.

The horizontal sidewall style

Prohibitor

TM

 HEC-12 PRO sprinklers

are recessed into the mounting
surface with only a portion of the heat
collecting fin assembly projecting into
the protected space.  The heat
collecting assembly has an average
breakaway load of 68 lbs., and a
maximum breakaway load of 85 lbs.
Unlike other institutional sprinklers,
the escutcheon plate and optional
closure plates are firmly attached to
the recessed sprinkler body with
tamper resistant retaining screws.

The Omega Prohibitor

TM

 sprinklers

are designed with an aesthetically
pleasing, low  profile silhouette.  They
feature a spray pattern that has been
shown to be effective in the control or
extinguishment of fire.

 The Model HEC-12 PRO is a

Horizontal Sidewall Sprinkler Listed
for standard sidewall applications with
the deflector positioned 4" to 12"
below the ceiling.

For all models of Prohibitor

TM

Sprinklers, an optional 3 5/8"
diameter light gauge escutcheon
closure plate is available, for use
where the wall penetration is greater

Omega HEC-12 PRO
Prohibitor

TM

Institutional
Automatic Sprinkler

7-92

HEC-12 PRO

OBSOLETE

Summary of Contents for CENTRAL Omega HEC-12 PRO Prohibitor

Page 1: ...is movement allows system water pressure to force the orifice sealing mechanism and deflector assembly open Water is then discharged in a designed flow pattern The Omega ProhibitorTM Model HEC 12 PRO Automatic Sprinklers have been specifically designed for use in institutional occupancies such as correctional facilities and mental health facilities where the occupants may attempt to tamper with or...

Page 2: ...ng 1 N P T Steel Nipple 1 x 1 2 N P T Reducer Escutcheon Tamper Resistant Screw 2 1 4 Dia Hole In Wall 2 1 2 Escutcheon 3 5 8 Dia Escutcheon Closure Plate 1 2 1 7 16 1 16 No Closure Plate 1 3 8 1 16 Escutcheon Closure Plate 1 5 16 1 16 Security Closure Plate 4 1 2 Dia Security Closure Plate 1 4 1 16 3 4 3 8 2 3 4 Shown for reference only not a height restriction 4 to 12 14 0 throw Centerline of Ro...

Page 3: ...he male threads only Step 4 Hand tighten the sprinkler into the reducing coupling Use an Omega HEC sprinkler wrench to tighten the unit into the fitting A leak tight joint requires the application of only 7 to 14 ft lbs of torque A tangential force of 14 to 28 lbs delivered through a 6 long handle will deliver adequate torque Torque levels over 21 ft lbs may distort the orifice seal resulting in l...

Page 4: ...tivity Do not attempt to re assemble or otherwise reuse a sprinkler that has operated Replace any sprinkler exhibiting corrosion or damage always use new sprinklers of the same type and temperature rating as replacements Because the discharge pattern is critical to protection of life and property nothing should be hung or attached to the sprinkler unit that would disrupt the discharge pattern Such...