13 Appendix – Configuration file parameters
Monitor ID
ID_1 - ID_16
1-65535
Unique Monitor ID. The
ID can be read on the
Monitor label.
Relay settings
RELAY_MODE
OFF,
ALARM_ROOF,
ALARM_MONITOR,
ALARM_ROOF_
MONITOR,
TEMP_ONESETPOINT,
TEMP_TWOSETPOINTS
[Factory setting: OFF]
RELAY_TEMP_HYSTERESIS
0 to 5 (°C)
[Factory setting: 1]
RELAY_TEMP_SETPOINT_1
-10 to 15 (°C)
[Factory setting: 8]
RELAY_TEMP_SETPOINT_2
-10 to 15 (°C)
[Factory setting: -2]
General settings
RF_ region
EU
Wireless frequency 868
MHz
Roof Alarm settings
ID_1 – ID_16 Offset
-5 to 5
[Factory setting: 0]
SAMPLE_NUMBER
1 to 255
[Factory setting: 4]
SAMPLE_PERIOD
1 to 255
[Factory setting: 1]
BLOCKED_SENSOR_LIMIT_FACTOR
1 to 255
[Factory setting: 20]
BLOCKED_SENSOR_ALARM_SET_COUNTER
1 to 255
[Factory setting: 5]
BLOCKED_SENSOR_NOALARM_RESET_
COUNTER
1 to 255
[Factory setting: 4]
BLOCKED_DRAIN_LIMIT_FACTOR
1 to 255
[Factory setting: 20]
BLOCKED_DRAIN_ALARM_SET_COUNTER
1 to 255
[Factory setting: 15]
BLOCKED_DRAIN_NOALARM_RESET_COUNTER
1 to 255
[Factory setting: 4]
BMS settings
BMS_SLAVE_ADDRESS
1 to 247
Modbus slave address of
a Gateway
[Factory setting: 1]
BMS_BAUDRATE
1200, 2400, 4800,
9600, 19200, 38400,
57600, 76800, 115200
Communication speed
[Factory setting: 19200]
BMS_PARITY
EVEN, ODD, NONE
[Factory setting: EVEN]
BMS_FRAMING
1STOPBIT, 2STOPBITS
[Factory setting:
1STOPBIT]
BMS_GATEWAY_TAG
String up to 32 ASCII
characters
[Factory setting:
WATTSELEC-3 ]
BMS_MONITOR1_TAG - BMS_MONITOR16_TAG
String up to 32 ASCII
characters
[Factory setting: Monitor1
- Monitor16]