background image

757 OSY

RP/IS-757/757DCDA

®

Installation, Maintenance, & Repair 

Series 757, 757DCDA & LF757DCDA

Double Check Valve Assemblies 

Double Check Detector Assemblies

Sizes: 2

1

2

" – 10"

 

NOTICE

For 

Australia

 and 

New Zealand

, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow pre-

venter.

Testing

For field testing procedure, refer to Watts installation sheets  

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on  

watts.com.

For other repair kits and service parts, refer to our Backflow 

Prevention Products Repair Kits & Service Parts price list  

PL-RP-BPD found on 

watts.com.

For technical assistance, contact your local Watts representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can 

result in death, serious personal injury, property damage, or 

damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing 
codes prior to installation.  If the information in this manual 
is not consistent with local building or plumbing codes, 
the local codes should be followed. Inquire with governing 
authorities for additional local requirements.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product must 

be tested periodically in compliance with local codes, but at least 

once per year or more as service conditions warrant. If installed on 

a fire suppression system, all mechanical checks, such as alarms 

and backflow preventers, should be flow tested and inspected in 

accordance with NFPA 13 and/or NFPA 25.  All products must be 

retested once maintenance has been performed. Corrosive water 

conditions, and/or unauthorized adjustments or repair could render 

the product ineffective for the service intended. Regular checking 

and cleaning of the product’s internal components helps assure 

maximum life and proper product function.

WARNING

!

Most field problems occur because dirt and debris present in the 

system at the time of installation become trapped in the #1 check. 

The system should be flushed before the backflow valve is 

installed.

 If the system is not flushed until after the backflow valve 

is installed, remove both check modules from the valve and open 

the inlet shutoff to allow water to flow for a sufficient time to flush 

debris from the water line. If debris in the water system continues 

to cause fouling, a strainer can be installed upstream of the back-

flow assembly.

Watts Series 757 and 757DCDA/LF757DCDA may be installed in 

either horizontal or vertical position as long as the backflow assem-

bly is installed in accordance with the direction of the flow arrow 

on the assembly and the local water authority approves the instal-

lation. The assembly should be installed with adequate clearance 

around the valve to allow for inspection, testing and servicing. 12" 

should be the minimum clearance between the lower portion of the 

assembly and the floor or grade.

NOTICE

  

Assembly body should not be painted.

Installation Guidelines

Отзывы: