WARNING

!

Prior to servicing any Watts valve, it is mandatory to shut down 

the water system by closing both the inlet and outlet shutoff 

valves. After shutoff valves are closed, open test cock #2, #3 

and #4 to relieve pressure within the backflow assembly.

1.  After #3 test cock has been opened to relieve pressure, 

remove #3 test cock from housing. (Figure A)

2.  Insert a #3 screwdriver through the hole on the top of the 

cover sleeve and using both hands rotate the cover sleeve 

approximately 

1

/

4

-turn clockwise and 

1

/

4

-turn counterclock-

wise to break the sleeve O-ring seals. Using the screwdriver, 

slowly slide the cover sleeve to the downstream side of the 

housing. (Figure B)

3.  Remove the stainless steel check retainer from the housing. 

(Figure B)

4.  Remove the #1 check module (Figure C) by inserting two flat 

blade screwdrivers into the slots on either side of the check 

module and gently pry the check module toward the open 

zone.

5.  Remove #2 check module with the same instructions as in #4 

above. For servicing 6" checks, see 8" – 10" instructions on 

p. 3.

6.  To clean or inspect either check module, insert a #3 screw-

driver through the downstream side of the check module as 

shown in Figure D and E. When the screwdriver is in place, 

remove the E-clip (Figure F) and pin connecting the structural 

members and the check clapper will open with no tension.

7.  Thoroughly clean the seating area. The sealing disc may be 

removed, if necessary, by removing the screws connecting 

the keeper plate to the clapper. The sealing disc may be 

reversed and reinstalled if the elastomer is cut or damaged.

8.  Wash check module and O-ring and inspect for any damage. 

If damaged, reinstall new parts.

9.  After thorough cleaning, lubricate O-ring w/FDA approved 

lubricant, replace pin and E-clip in structural members, 

remove screw driver and reinstall check modules and assem-

ble housing in reverse order of these instructions.

Maintenance Instructions