ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
94
of
140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
5
Flame Strength
SMD_BAS_IP_HTR_05_[8]
✓
AV:708
Data Float
134
nvoHTR_05_9 inc count (9)
Output (non-polled)
30708
5
Fire Rate In
SMD_BAS_IP_HTR_05_[9]
✓
AV:709
Data Float
135
nvoHTR_05_10 inc count (9)
Output (non-polled)
30709
5
Fire Rate Out
SMD_BAS_IP_HTR_05_[10]
✓
AV:710
Data Float
136
nvoHTR_05_11 inc count (9)
Output (non-polled)
30710
5
Unit Type
SMD_BAS_IP_HTR_05_[11]
✓
AV:711
Data Float
137
nvoHTR_05_12 inc count (9)
Output (non-polled)
30711
5
Unit Size
SMD_BAS_IP_HTR_05_[12]
✓
AV:712
Data Float
138
nvoHTR_05_13 inc count (9)
Output (non-polled)
30712
5
Value State
SMD_BAS_IP_HTR_05_[13]
✓
AV:713
Data Float
139
nvoHTR_05_14 inc count (9)
Output (non-polled)
30713
5
Net Remote Setpt
SMD_BAS_IP_HTR_05_[14]
✓
AV:714
Data Float
140
nvoHTR_05_15 inc count (9)
Output (non-polled)
30714
5
Run Cycles Upper
SMD_BAS_IP_HTR_05_[15]
✓
AV:715
Data Float
141
nvoHTR_05_16 inc count (9)
Output (non-polled)
30715
5
Run Cycles Lower
SMD_BAS_IP_HTR_05_[16]
✓
AV:716
Data Float
142
nvoHTR_05_17 inc count (9)
Output (non-polled)
30716
5
Run Hours Upper
SMD_BAS_IP_HTR_05_[17]
✓
AV:717
Data Float
143
nvoHTR_05_18 inc count (9)
Output (non-polled)
30717
5
Run Hours Lower
SMD_BAS_IP_HTR_05_[18]
✓
AV:718
Data Float
144
nvoHTR_05_19 inc count (9)
Output (non-polled)
30718
5
Oxygen Level
SMD_BAS_IP_HTR_05_[19]
✓
AV:719
Data Float
145
nvoHTR_05_20 inc count (9)
Output (non-polled)
30719
Blr Addr 6
6
Comm Address
SMD_BAS_IP_HTR_06_[0]
✓
AV:800
Data Float
146
nvoHTR_06_1
inc count (9)
Output (non-polled)
30800
6
Unit Status
SMD_BAS_IP_HTR_06_[1]
✓
AV:801
Data Float
147
nvoHTR_06_2
inc count (9)
Output (non-polled)
30801
6
Fault Code
SMD_BAS_IP_HTR_06_[2]
✓
AV:802
Data Float
148
nvoHTR_06_3
inc count (9)
Output (non-polled)
30802
6
Outlet Temp
SMD_BAS_IP_HTR_06_[3]
✓
AV:803
Data Float
149
nvoHTR_06_4
inc count (9)
Output (non-polled)
30803
6
FFWD Temp
SMD_BAS_IP_HTR_06_[4]
✓
AV:804
Data Float
150
nvoHTR_06_5
inc count (9)
Output (non-polled)
30804
6
Inlet Temp
SMD_BAS_IP_HTR_06_[5]
✓
AV:805
Data Float
151
nvoHTR_06_6
inc count (9)
Output (non-polled)
30805
6
Exhaust Temp
SMD_BAS_IP_HTR_06_[6]
✓
AV:806
Data Float
152
nvoHTR_06_7
inc count (9)
Output (non-polled)
30806
6
Air Temp
SMD_BAS_IP_HTR_06_[7]
✓
AV:807
Data Float
153
nvoHTR_06_8
inc count (9)
Output (non-polled)
30807
6
Flame Strength
SMD_BAS_IP_HTR_06_[8]
✓
AV:808
Data Float
154
nvoHTR_06_9
inc count (9)
Output (non-polled)
30808
6
Fire Rate In
SMD_BAS_IP_HTR_06_[9]
✓
AV:809
Data Float
155
nvoHTR_06_10
inc count (9)
Output (non-polled)
30809
6
Fire Rate Out
SMD_BAS_IP_HTR_06_[10]
✓
AV:810
Data Float
156
nvoHTR_06_11
inc count (9)
Output (non-polled)
30810