ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX J: REFERENCE
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
137
of
140
Appendix J: REFERENCE
Appendix J-1: Specifications
ProtoNode FPC-N34
ProtoNode FPC-N35
Electrical
Connections:
One 6-pin Phoenix connector
with:
RS-485 port (+ / - / gnd)
Power port (+ / - / Frame-gnd)
One 3-pin Phoenix connector
with:
RS-485 port (+ / - / gnd)
One Ethernet 10/100 BaseT
port
One 6-pin Phoenix connector
with:
RS-485 port (+ / - / gnd)
Power port (+ / - / Frame-gnd)
One Ethernet 10/100 BaseT port
One FTT-10 LonWorks port
Approvals:
CE Certified; TUV approved to UL 916, EN 60950-1, EN 50491-3 and
CSA C22-2 standards;
FCC Class A Part 15; DNP3 Conformance Tested;
RoHS Compliant; CSA 205 Approved
BTL Marked
LonMark Certified
Power
Requirements:
Multi-mode power adapter: 9-30VDC or 12 - 24VAC
Physical
Dimensions:
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Weight:
0.2 kg (0.4 lbs)
Operating
Temperature:
-40°C to 75°C (-40°F to167°F)
Surge Suppression:
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity:
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Figure J-1: Specifications
Appendix J-2: Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating ProtoNode.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected
operating temperature range.
•
The interconnecting power connector and power cable shall:
o
Comply with local electrical code.
o
Be suited to the expected operating temperature range.
o
Meet the current and voltage rating for ProtoNode/Net
•
Furthermore, the interconnecting power cable shall:
o
Be of length not exceeding 3.05m (118.3”)