ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
100
of
140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
12
Comm Address
SMD_BAS_IP_HTR_12_[0]
✓
AV:1400
Data Float
266
nvoHTR_12_1 inc count (9)
Output (non-polled)
31400
12
Unit Status
SMD_BAS_IP_HTR_12_[1]
✓
AV:1401
Data Float
267
nvoHTR_12_2 inc count (9)
Output (non-polled)
31401
12
Fault Code
SMD_BAS_IP_HTR_12_[2]
✓
AV:1402
Data Float
268
nvoHTR_12_3 inc count (9)
Output (non-polled)
31402
12
Outlet Temp
SMD_BAS_IP_HTR_12_[3]
✓
AV:1403
Data Float
269
nvoHTR_12_4 inc count (9)
Output (non-polled)
31403
12
FFWD Temp
SMD_BAS_IP_HTR_12_[4]
✓
AV:1404
Data Float
270
nvoHTR_12_5 inc count (9)
Output (non-polled)
31404
12
Inlet Temp
SMD_BAS_IP_HTR_12_[5]
✓
AV:1405
Data Float
271
nvoHTR_12_6 inc count (9)
Output (non-polled)
31405
12
Exhaust Temp
SMD_BAS_IP_HTR_12_[6]
✓
AV:1406
Data Float
272
nvoHTR_12_7 inc count (9)
Output (non-polled)
31406
12
Air Temp
SMD_BAS_IP_HTR_12_[7]
✓
AV:1407
Data Float
273
nvoHTR_12_8 inc count (9)
Output (non-polled)
31407
12
Flame Strength
SMD_BAS_IP_HTR_12_[8]
✓
AV:1408
Data Float
274
nvoHTR_12_9 inc count (9)
Output (non-polled)
31408
12
Fire Rate In
SMD_BAS_IP_HTR_12_[9]
✓
AV:1409
Data Float
275
nvoHTR_12_10 inc count (9)
Output (non-polled)
31409
12
Fire Rate Out
SMD_BAS_IP_HTR_12_[10]
✓
AV:1410
Data Float
276
nvoHTR_12_11 inc count (9)
Output (non-polled)
31410
12
Unit Type
SMD_BAS_IP_HTR_12_[11]
✓
AV:1411
Data Float
277
nvoHTR_12_12 inc count (9)
Output (non-polled)
31411
12
Unit Size
SMD_BAS_IP_HTR_12_[12]
✓
AV:1412
Data Float
278
nvoHTR_12_13 inc count (9)
Output (non-polled)
31412
12
Value State
SMD_BAS_IP_HTR_12_[13]
✓
AV:1413
Data Float
279
nvoHTR_12_14 inc count (9)
Output (non-polled)
31413
12
Net Remote Setpt
SMD_BAS_IP_HTR_12_[14]
✓
AV:1414
Data Float
280
nvoHTR_12_15 inc count (9)
Output (non-polled)
31414
12
Run Cycles Upper
SMD_BAS_IP_HTR_12_[15]
✓
AV:1415
Data Float
281
nvoHTR_12_16 inc count (9)
Output (non-polled)
31415
12
Run Cycles Lower
SMD_BAS_IP_HTR_12_[16]
✓
AV:1416
Data Float
282
nvoHTR_12_17 inc count (9)
Output (non-polled)
31416
12
Run Hours Upper
SMD_BAS_IP_HTR_12_[17]
✓
AV:1417
Data Float
283
nvoHTR_12_18 inc count (9)
Output (non-polled)
31417
12
Run Hours Lower
SMD_BAS_IP_HTR_12_[18]
✓
AV:1418
Data Float
284
nvoHTR_12_19
inc count (9)
Output (non-polled)
31418
12
Oxygen Level
SMD_BAS_IP_HTR_12_[19]
✓
AV:1419
Data Float
285
nvoHTR_12_20
inc count (9)
Output (non-polled)
31419
Blr Addr 13
13
Comm Address
SMD_BAS_IP_HTR_13_[0]
✓
AV:1500
Data Float
286
nvoHTR_13_1 inc count (9)
Output (non-polled)
31500
13
Unit Status
SMD_BAS_IP_HTR_13_[1]
✓
AV:1501
Data Float
287
nvoHTR_13_2 inc count (9)
Output (non-polled)
31501
13
Fault Code
SMD_BAS_IP_HTR_13_[2]
✓
AV:1502
Data Float
288
nvoHTR_13_3 inc count (9)
Output (non-polled)
31502