Watt Stopper DT-200 Скачать руководство пользователя страница 4

WIRING DIRECTIONS

Each WattStopper BZ series power pack can supply power for 3 DT-200 sensors. 

When using more sensors than this, multiple power packs are required.
Refer to the wiring diagram on the next page for the following procedures:
Connect the 

LOW VOLTAGE:

 

• 

RED wire (+24VDC) from power pack to the 

red 

wire on the sensor. 

• 

BLACK wire (Return) from power pack to the 

black

 wire on the sensor.

Wiring a 

single lighting load controlled by occupancy

–connect:

• 

BLUE wire from power pack to the 

blue

 wire on the sensor.

To add a 

Momentary manual switch

 such as the LVSW Momentary Toggle Switch, to 

the above applications–connect:

• 

Wire from one side of switch to the 

grey

 wire on sensor.

• 

Wire from other side of switch to the 

red

 wire on sensor.

Wiring the 

Isolated Relay

: (The Isolated Relay is rated for 1A@30VAC/VDC)

 Connect the wires necessary to the application that requires this output:

• 

Relay Common (must be used for proper operation) is the 

green

 wire

• 

N.O. (Normally Open)–Closed when occupancy is detected, is the 

orange

 wire

• 

N.C. (Normally Closed)–Open when occupancy is detected, is the 

brown

 wire

Sensor Function

DT-200 ver.3 DT-200 ver.2

BZ-50 PP

+24VDC in

RED

Violet

RED

Common to Power Pack

BLACK

Grey

BLACK

Control Output

BLUE

Yellow

BLUE

Isolated Relay Common

GREEN

Red

Isolated Relay N.O.

ORANGE

Orange

Isolated Relay N.C.

BROWN

Brown

Momentary Switch

GREY

Green

Light Level Control Output

N/A

Blue

CAUTION

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE 

INSTALLING POWER PACKS OR SENSORS.

Call 800.879.8585 for Technical Support

Содержание DT-200

Страница 1: ...g Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC to 200FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec...

Страница 2: ...nutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 200 operates on 24VDC suppli...

Страница 3: ...erage patterns As a general rule each occupant should be able to clearly view the sensor Masking the PIR Lens Opaque adhesive tape is supplied so that sections of the PIR lens can be masked This restr...

Страница 4: ...wire on sensor Wire from other side of switch to the red wire on sensor Wiring the Isolated Relay The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requ...

Страница 5: ...osed Contact Orange Normally Open Contact Green Common Isolated Relay Outputs Grey Man Switch DT 200v3 Occupancy Sensor Grey wire on sensor is only used when connecting a manual momentary switch LVSW...

Страница 6: ...racket so that it is in line with the half circle notch as illustrated in figure A Push the ball into the Base Bracket opening until it snaps into place being careful not to pinch the wires The bracke...

Страница 7: ...htening Screw to hold this position Wall Mount PARALLEL to WALL at 10 foot mounting height Reference Surface Angle Ceiling Mount PARALLEL to VERTICAL at 10 foot mounting height Reference Surface Angle...

Страница 8: ...ll not return it to previous settings If Test Mode is enabled after Light Level has been set Light Level functionality will cease to function throughout the duration of Test Mode When Test Mode period...

Страница 9: ...or more resets the light to default maximum Press and hold the Light Level button for 5 seconds or until the detection LEDs turn ON and then OFF The LEDs flash rapidly for 10 seconds after the settin...

Страница 10: ...re that the Ultrasonic Sensitivity trimpot is set to about 70 clockwise 4 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 M...

Страница 11: ...od that activates a change from Standby area unoccupied and loads are OFF to Occupied area occupied and loads are ON Both requires detection by PIR and Ultrasonic Either requires detection by only one...

Страница 12: ...manual switch and it stays on according to the occupancy logic setting The time delay operates as programmed When the load turns OFF due to lack of occupancy detection it can be turned ON again by oc...

Страница 13: ...h voltage is present replace the power pack Red LED does not flash 1 When power is initially applied to the sensor there is a warm up period of 30 to 60 seconds before the LED becomes active 2 Make su...

Страница 14: ...corrected the sensor will return to normal operation Check the blue wire connection If necessary replace the power pack Lights do not turn off automatically Green LED flashes Reduce ultrasonic sensit...

Страница 15: ...sensor to time out If lights turn off the sensor is working properly adjust sensitivity and time delay for the sensor If lights do not turn off check the wiring between the sensor and power pack If w...

Страница 16: ...profit or cost of removal installation or reinstallation ORDERING INFORMATION Catalog Description DT 200 Dual Technology Occupancy Sensor Low Voltage w Isolated Relay DT 205 Dual Technology Occupancy...

Отзывы: