Red and Green LEDs flash 

1.  Check all sensor and power pack connections.
2.  Check if Light Level is enabled.  

• 

If occupancy indicator LEDs blink together every few seconds, sensor is 

using Light Level feature.  

• 

If Light Level functionality is not desired, press and hold for 5 seconds to 

return sensor to the default setting (maximum). 

3.  Check for 24VDC at the power pack blue and black wire connections to sensor 

while sensor is active.

• 

If there is no voltage, replace the sensor.

• 

If there is voltage, check for 24VDC between the blue and black wire at the 

power pack.  If 24VDC is present and the relay is not closing, replace it.

• 

 If 24VDC is not present, check for a break in the low voltage wiring.

4.  If LEDs are flashing rapidly (~10Hz), an overload condition exists. When this 

is corrected, the sensor  will return to normal operation. Check the blue wire 
connection. If necessary, replace the power pack.

Lights do not turn off automatically.

Green LED flashes  

Reduce ultrasonic sensitivity by turning adjustment pot counter-clockwise until it 

only flashes when movement occurs.

Red LED flashes briefly and Green LED does not flash 

Check to see if you have used the Manual Switch connection.  Do not connect 

anything to this terminal if you are not using a low voltage momentary switch 

between the sensor and power pack.

Red LED randomly flashes 

Set PIR sensitivity to minimum by turning DIP switch 5 to the “on” position.

Lights do not turn off 

1.  Check all sensor and power pack wire connections.
2.  Disconnect power pack blue wire.

• 

If lights do not turn off, check power pack wiring.  Replace the power pack 

if necessary.

• 

If lights turn off, the problem may be the sensor or wiring between the 

sensor and power pack.

Call 800.879.8585 for Technical Support

Содержание DT-200

Страница 1: ...g Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC to 200FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec...

Страница 2: ...nutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 200 operates on 24VDC suppli...

Страница 3: ...erage patterns As a general rule each occupant should be able to clearly view the sensor Masking the PIR Lens Opaque adhesive tape is supplied so that sections of the PIR lens can be masked This restr...

Страница 4: ...wire on sensor Wire from other side of switch to the red wire on sensor Wiring the Isolated Relay The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requ...

Страница 5: ...osed Contact Orange Normally Open Contact Green Common Isolated Relay Outputs Grey Man Switch DT 200v3 Occupancy Sensor Grey wire on sensor is only used when connecting a manual momentary switch LVSW...

Страница 6: ...racket so that it is in line with the half circle notch as illustrated in figure A Push the ball into the Base Bracket opening until it snaps into place being careful not to pinch the wires The bracke...

Страница 7: ...htening Screw to hold this position Wall Mount PARALLEL to WALL at 10 foot mounting height Reference Surface Angle Ceiling Mount PARALLEL to VERTICAL at 10 foot mounting height Reference Surface Angle...

Страница 8: ...ll not return it to previous settings If Test Mode is enabled after Light Level has been set Light Level functionality will cease to function throughout the duration of Test Mode When Test Mode period...

Страница 9: ...or more resets the light to default maximum Press and hold the Light Level button for 5 seconds or until the detection LEDs turn ON and then OFF The LEDs flash rapidly for 10 seconds after the settin...

Страница 10: ...re that the Ultrasonic Sensitivity trimpot is set to about 70 clockwise 4 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 M...

Страница 11: ...od that activates a change from Standby area unoccupied and loads are OFF to Occupied area occupied and loads are ON Both requires detection by PIR and Ultrasonic Either requires detection by only one...

Страница 12: ...manual switch and it stays on according to the occupancy logic setting The time delay operates as programmed When the load turns OFF due to lack of occupancy detection it can be turned ON again by oc...

Страница 13: ...h voltage is present replace the power pack Red LED does not flash 1 When power is initially applied to the sensor there is a warm up period of 30 to 60 seconds before the LED becomes active 2 Make su...

Страница 14: ...corrected the sensor will return to normal operation Check the blue wire connection If necessary replace the power pack Lights do not turn off automatically Green LED flashes Reduce ultrasonic sensit...

Страница 15: ...sensor to time out If lights turn off the sensor is working properly adjust sensitivity and time delay for the sensor If lights do not turn off check the wiring between the sensor and power pack If w...

Страница 16: ...profit or cost of removal installation or reinstallation ORDERING INFORMATION Catalog Description DT 200 Dual Technology Occupancy Sensor Low Voltage w Isolated Relay DT 205 Dual Technology Occupancy...

Отзывы: