UNIT DESCRIPTION

The WattStopper DT-200 Dual Technology occupancy sensors combine advanced 

passive infrared (PIR) and ultrasonic technologies into one unit. The combination 

of these technologies helps to eliminate false triggering problems even in difficult 

applications. 
The DT-200 turns lighting systems on and off based on occupancy and ambient light 

levels.  
The DT-200 offers numerous operating modes that can be combined to create the 

ideal custom control. The sensors can be configured to turn lighting on, and hold it 

on as long as either or both technologies detect occupancy. After no movement is 

detected for the duration of the time delay (30 seconds to 30 minutes) the lights are 

switched off. A “walk-through” mode can turn lights off after only 3 minutes, if no 

activity is detected after 30 seconds of an occupancy detection.
The DT-200 operates on 24VDC supplied by WattStopper Power Packs. DT-200 

sensors also have an isolated relay with Normally Open and Normally Closed 

contacts for interfacing with HVAC or EMS.

COVERAGE PATTERN

The DT-200 provides an eliptical coverage pattern. The coverage shown represents 

walking motion at a mounting height of 10 feet. For building spaces with lower 

levels of activity or with obstacles and barriers, coverage size may decrease.

10 ft

Dense Wide Angle Lens (Standard)

7 ft

15 ft

25 ft

55ft

0

PIR
coverage
55ft.

Ultrasonic
coverage
38ft.

Dense Wide Angle Lens

up to 2000 sq ft for walking motion

up to 1000 sq ft for desktop motion

(Drawings not to scale.)

Call 800.879.8585 for Technical Support

Содержание DT-200

Страница 1: ...g Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC to 200FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec...

Страница 2: ...nutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 200 operates on 24VDC suppli...

Страница 3: ...erage patterns As a general rule each occupant should be able to clearly view the sensor Masking the PIR Lens Opaque adhesive tape is supplied so that sections of the PIR lens can be masked This restr...

Страница 4: ...wire on sensor Wire from other side of switch to the red wire on sensor Wiring the Isolated Relay The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requ...

Страница 5: ...osed Contact Orange Normally Open Contact Green Common Isolated Relay Outputs Grey Man Switch DT 200v3 Occupancy Sensor Grey wire on sensor is only used when connecting a manual momentary switch LVSW...

Страница 6: ...racket so that it is in line with the half circle notch as illustrated in figure A Push the ball into the Base Bracket opening until it snaps into place being careful not to pinch the wires The bracke...

Страница 7: ...htening Screw to hold this position Wall Mount PARALLEL to WALL at 10 foot mounting height Reference Surface Angle Ceiling Mount PARALLEL to VERTICAL at 10 foot mounting height Reference Surface Angle...

Страница 8: ...ll not return it to previous settings If Test Mode is enabled after Light Level has been set Light Level functionality will cease to function throughout the duration of Test Mode When Test Mode period...

Страница 9: ...or more resets the light to default maximum Press and hold the Light Level button for 5 seconds or until the detection LEDs turn ON and then OFF The LEDs flash rapidly for 10 seconds after the settin...

Страница 10: ...re that the Ultrasonic Sensitivity trimpot is set to about 70 clockwise 4 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 M...

Страница 11: ...od that activates a change from Standby area unoccupied and loads are OFF to Occupied area occupied and loads are ON Both requires detection by PIR and Ultrasonic Either requires detection by only one...

Страница 12: ...manual switch and it stays on according to the occupancy logic setting The time delay operates as programmed When the load turns OFF due to lack of occupancy detection it can be turned ON again by oc...

Страница 13: ...h voltage is present replace the power pack Red LED does not flash 1 When power is initially applied to the sensor there is a warm up period of 30 to 60 seconds before the LED becomes active 2 Make su...

Страница 14: ...corrected the sensor will return to normal operation Check the blue wire connection If necessary replace the power pack Lights do not turn off automatically Green LED flashes Reduce ultrasonic sensit...

Страница 15: ...sensor to time out If lights turn off the sensor is working properly adjust sensitivity and time delay for the sensor If lights do not turn off check the wiring between the sensor and power pack If w...

Страница 16: ...profit or cost of removal installation or reinstallation ORDERING INFORMATION Catalog Description DT 200 Dual Technology Occupancy Sensor Low Voltage w Isolated Relay DT 205 Dual Technology Occupancy...

Отзывы: