Wiring
Page 30 / 52
Terminal
categorie
Symbol
Purpose
Initial setting
Remarks
5
Reset input
4
Multistage frequency
input / USP function
3
Multistage frequency
input / use 4-20mA
input
2
Reverse run
1
These inputs have different
purposes depending on the user
programmed configuration:
Forward and reverse running
command, up to 4 multistage
speed settings, jogging run, 2nd
stage acceleration/decel., free run
stop, external trip, USP function,
terminal software lock, reset,
PTC, input for choosing current
as analog set value
Forward run
Input closed (ON):
Function active
Input opened (OFF):
Function not active
Input must be ON for
a
minimum of 12ms
Digital
Inputs
P24
Common for input signals
24V DC; max. 30mA
FM
Connection of an analog or digital
meter for measuring frequency;
connection of an analog meter for
current measurement
Frequency monitor
(analog)
Monitor
signal
L
Common for monitor signal
H
Reference for frequency
command input
10V DC; max. 10mA
O
Voltage frequency command
Set value 0-10V;
Input impedance 10k
Ohm
OI
Current frequency command
Set value 4-20mA;
Input impedance 250
Ohm
Frequency
command
input
L
Common for frequency command
input
11
Frequency arrival
signal (signal when
reaching
set value)
12
The digital outputs can be user
programmed to provide different
signals for the following
situations:
Signal when reaching set value or
passing a configurable frequency;
signal during motor run;
overload signal;
PID deviation signal; alarm signal
Signal during
motor run
Outputs of
open collector type
for connection to a
relay
(max. 27V DC and
max. 50mA)
Digital
output
CM2
Common for digital outputs
AL0
AL1
Fault
alarm
output
AL2
AL0 AL1 AL2
Initial setting: During normal operation AL0-AL1 is closed; during a trip
condition
or cut off power supply AL0-AL1 is opened (i.e. AL0-AL2 is closed).
Ratings of relay contacts:
Max. 250VAC / 2.5A (resistive) or 0.2A (cos phi = 0.4); Min. 100VAC /
10mA
Max. 30VDC / 3.0A (resistive) or 0.7A (cos phi = 0.4); Min. 5VDC /
100mA