Wiring
Page 26 / 52
Wiring equipment and options
CAUTION Provide the wiring equipment in accordance with the safety codes required
by jurisdictional authorities. If specified in standards or laws and regulations,
follow their istructions. In the following table some guidelines for choosing an
appropriate wire gauge are presented:
Cable specifications
Motor
output
(kW)
Inverter
model
Power lines
Signal
lines
600V fuse to be
used
(rated current / A)
0.2
L2000-002NFE
0.4
L2000-004NFE
0.55
L2000-005NFE
1.5 mm
2
(AWG 15)
10 A
0.75
L2000-007NFE
1.1
L2000-011NFE
2.5 mm
2
(AWG 13)
16 A
1.5
L2000-015NFE
4.0 mm
2
(AWG 11)
25 A (single phase)
16 A (three phase)
2.2
L2000-022NFE
4.0 mm
2
(AWG 11)
40 A (single phase)
25 A (three phase)
0.4
L2000-004HFE
1.5 mm
2
(AWG 15)
10 A
0.75
L2000-007HFE
1.5 mm
2
(AWG 15)
2.5 mm
2
(AWG 13)
10 A
16 A
1.5
L2000-015HFE
1.5 mm
2
(AWG 15)
2.5 mm
2
(AWG 13)
2.5 mm
2
(AWG 13)
4.0 mm
2
(AWG 11)
10 A
16 A
16 A
25 A
2.2
L2000-022HFE
3.0
L2000-030HFE
4.0
L2000-040HFE
5.5
L2000-055HFE
1.5 mm
2
(AWG 15)
2.5 mm
2
(AWG 13)
2.5 mm
2
(AWG 13)
4.0 mm
2
(AWG 11)
2.5 mm
2
(AWG 13)
4.0 mm
2
(AWG 11)
4.0 mm
2
(AWG 11)
10 A
16 A
16 A
25 A
16 A
25 A
25 A
7.5
L2000-075HFE
2.5 mm
2
(AWG 13)
4.0 mm
2
(AWG 11)
4.0 mm
2
(AWG 11)
4.0 mm
2
(AWG 11)
16 A
25 A
25 A
25 A
4.0 mm
2
(AWG 11)
S
hi
el
ded
w
ire (m
ax. 0.75mm
2
)
*)
25 A
Содержание L2000 Series
Страница 1: ...INVERTER Series L2000 M A N U A L NB596XA...