Safety precautions
Page 12 / 52
CAUTION Check the following during and after the test run. Otherwise, there is a
danger of machine breakage:
Was the short cut bar between ter1 and + removed by mistake?
Was the running direction of the motor correct?
Was the inverter tripped during acceleration or deceleration?
Were the indications of the rpm and the frequency meter correct?
Were there any abnormal motor vibrations or noise?
Maintenance and inspection
WARNING Before carrying out maintenance and inspection wait for at least five minutes
after having turned off the input power supply. Otherwise, there is a danger of
electric shock.
WARNING When removing connectors (e.g. from fans and printed circuit boards) never
pull the attached wires. Otherwise, there is a danger of fire due to wire
breakage and/or injury.
Others
CAUTION
Withstand voltage tests and insulation resistance tests (megger tests) are
executed before the units are shipped, so that there is no need to conduct
these tests before operation.
CAUTION
Do not attach or remove wiring or connectors when power is applied. Also, do
not check signals (e.g. using a multimeter) during operation.
CAUTION
Never stop motor operation by switching off the electromagnetic contactors on
the primary or secondary side of the inverter.
Motor
Inverter
Earth leakage
circuit breaker
L1(L1)
L2
L3(N)
T1(U)
T2(V)
T3(W)
Power
supply
S2
FW
P24
CORRECT: Start and stop using FW terminal
S1
WRONG: Start and stop using
secondary side contactor
WRONG: Start and stop using
primary side contactor
When there has been an instantaneous power failure, and if an operation
instruction has been given, then the inverter may restart operation after the
power failure has ended. If there is a possibility that such an occurrence may
harm humans, then install an electromagnetic contactor on the primary (power
supply) side of the inverter, so that the circuit does not allow automatic
restarting after the power supply has recoverd. If the optional remote operator
is used and the retry function has been selected, this will also cause automatic
restarting when an operation instruction has been input, so please be careful.
CAUTION
Do not insert leading power factor capacitors or surge absorbers between the
output terminals of the inverter and the motor.
Motor
Inverter
Earth leakage
circuit breaker
L1(L1)
L2
L3(N)
T1(U)
T2(V)
T3(W)
Power
supply
WRONG: Capacitor
WRONG:
Surge absorber