19
PROFINET® mode
19.1
Behaviour on start up
IOPS = bad
If the Input Output Provider Status (IOPS) associated with a sub module is BAD (any value other than
0x80), then the I/O data of that sub module as viewed over PROFINET® will be cleared to zeroes. The
equivalent parameters viewed on the TFT screen, or over the web interface, are not cleared. Upon
receiving a network message with IOPS=BAD, no parameters of the pump that were attempted to be
written will be updated, and the Network Status LED will flash once in green. The pump will continue
to respond normally however, to any valid future messages. By default, the motor will stop if
IOPS=BAD, but this behaviour can be customised using the
failsafe
settings.
Disconnection
If a PROFINET® connection is aborted (for example, the Ethernet cable is disconnected), then the I/O
data of all sub modules as viewed over PROFINET® are cleared to zeroes. The equivalent parameters
viewed on the TFT screen, or over the web interface, are not cleared. New connections may be
established without needing to reboot the pump. By default, the motor will stop upon losing
connection, but this behaviour can be customised using the
failsafe
settings.
Mains power on
The I/O data of all sub modules as viewed over PROFINET® will be cleared to zeroes. This does not
clear the parameters stored on the pump itself.
By default, the motor is stopped on power on, however this behaviour can be modified using the
Auto Restart
setting, and also the
Resume Interrupted
setting if in
Dispense
mode.
Table 9 - PLC Errors
PLC Error
Pump Behaviour
IOPS = bad
Stopped – can be modified using the
failsafe
setting
Disconnected
connection
Stopped – can be modified using the
failsafe
setting
Mains power on
Stopped – can be modified using the
Auto Restart
and
Resume
Interrupted
setting
19.2
Configure PROFINET® settings
Table 10 - Configure PROFINET® settings
Setting
Value
DHCP Enable
Off
IP Address
192.168.001.012
Subnet mask
255.255.255.000
Gateway address
192.168.001.001
80
m-530pn-en-09 02-02-22
Содержание 530 Pn
Страница 33: ...12 7 Network topology Figure 17 Star network m 530pn en 09 02 02 22 33...
Страница 34: ...Figure 18 Ring network Figure 19 Line topology 34 m 530pn en 09 02 02 22...
Страница 69: ...3 Press HOME to return and store the setting The input is now disabled in Manual mode m 530pn en 09 02 02 22 69...
Страница 71: ...3 Press HOME to return and store the setting The input is now enabled in Manual mode m 530pn en 09 02 02 22 71...
Страница 72: ...15 6 Help Help 1 Select Help from the main menu to access the help screens 72 m 530pn en 09 02 02 22...
Страница 81: ...1 Press the MODE key to access the MODE menu 2 Use the keys to select PROFINET m 530pn en 09 02 02 22 81...
Страница 84: ...4 Press BACK to return to the MODE MENU 84 m 530pn en 09 02 02 22...
Страница 129: ...Procedure 1 From the GENERIC SENSOR VALUES screen 2 Using the keys scroll to Set slope adjust m 530pn en 09 02 02 22 129...