Output 1 Option “H”, O-5VDC

Model#  98_A-_H  _0-0000

Process Output
Proportional value determined by the control to balance the sensor input and set point.

This value will fall between O-5VDC dependlng on your process output type.

Output 2 Option “B”, Solid State Relay

Model# 98_A- 

B 0-0000

- -

Solid State Relay

Watlow’s solid state relays change state at zero volts, which is zero-cross switching.”
They are also optically isolated, which means the output circuitry is energized by 

infrared light striking a photo-sensitive device. This results  

in 

virtual absence of electri-

cally

 generated noise, 

plus output to input 

 electrical isolation. 

Off state impedance is

2    O    K    o   h   m   s minimum.

Figure 20 -

O-5VDC, Output 1,

Option "H" Wiring

Diagram.

Figure 21 -
S.S. Relay,
Output 2, Option "B"
Wiring Diagram.

Install and Wire, Chapter

 2

WATLOW Series 980/985 Users Manual

19

Содержание Micro-Based Autotuning Control SERIES...

Страница 1: ...Control User s Manual Watlow Controls 1241 Bundy Blvd P O 8ox 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 W985 MA58 9307 February 1993 Supersedes W985 MA70 9043 10 00 Made in the U S...

Страница 2: ...afety Information This user s manual also has boldface safety information notes to protect both you and your equipment Please be attentive to them Here are explanations A T The Caution symbol exclamat...

Страница 3: ...2 Shipping Claims 43 Warranty 43 Watlow Controls Chapter 1 Figure 4 5 10 10 10 12 12 13 13 14 14 15 15 16 16 l 17 18 18 19 19 20 20 21 22 23 24 24 27 31 32 37 38 Series 980 985 Input Output Overview 1...

Страница 4: ...T N or Platinel2 thermocouple RTD or process input The primary output is Heating or Cooling while the secondary output can be Heat Cool or Alarm With the Series 980 985 you can select either PID or O...

Страница 5: ...onfigure the 980 985 s features to your application Establish levels of operator access input type units of measure low and high range limits and Output 2 configuration Figure 2 Overview of the Series...

Страница 6: ...r flow past this sensor should be moderate The sensor should be thermally insulated from the sensor mounting Installation Guidelines For Preventing Noise For improved electrical noise immunity install...

Страница 7: ...or control Don t have phase angle fired devices in the same electrical enclosure or on the same power line with the control Shielded cables should be used for all low power signal lines to protect fro...

Страница 8: ...ork best Don tconnectgroundto the control case if the control is mounted in grounded enclosure prevent ground loops Do not confuse chassis grounds safety ground with control circuit commons or with AC...

Страница 9: ...nd termina tion Measure the resistance from the wire to the point where it was connected The ohmmeter should read a high ohm value If you have a low ohm value across this gap there is at least one gro...

Страница 10: ...ents ground loops and maintains filter effectiveness Differential Mode Filter Wiring Ll D M Line Filter NOTE Keep filters 12 inches or less from the control Minimize the line distance where nolse can...

Страница 11: ...f the case The first two shorter slots are for attaching the mounting brack ets Figure 8 shows a side view with both mounting brackets easier Loosen the mounting bracket screws with a Phillips screwdr...

Страница 12: ...Dimensions Panel Cutout Max Panel Thickness 0 50 12 7mm 3 82 0 03 0 00 92mm 0 8 LoadPower indicators V Panel TI 89 48 0 mm Figure 7 Series 980 985 Dimensions _ Adjustuble 12 WATLOW Series 9801985 User...

Страница 13: ...pplicable codes as well When you apply power without sensor inputs on the terminal strip the Series 980 985 will display in the Upper display and a O in the Lower display Press the AUTO MANUAL key twi...

Страница 14: ...junction with your units sensor type Thermocouple and RTD only Input Options 2 3 Process or Remote Set Point Input Terminals 15 17 Model 98_A 2 _ _ 0 0000 98_A 3 _ _ 0 0000 0 II Jumper Terminal 16 to...

Страница 15: ...two wire RTD That resistance when added to the resistance of the RTD element can result in erroneous input to the instrument To overcome this problem use a three wire RTD sensor which compensates for...

Страница 16: ...o input electrical isolation Off state impedance is 2OKohm minimum Output 1 Option C DC Output Open Collector Model 98_A _C_0 0000 71 3 Q DCLoad u Switched DC Watlow s solid state switch isa low curre...

Страница 17: ...e Common Contact of the relay Off state impedance is2OKohm minimum Output 1 Option E 0 I0 VDC Model 98_A _E _0 0000 Process Output Proportional value determined by the Control to balance the sensor in...

Страница 18: ...l to balance the sensor input and set point This value will fall between4 20mA depending on your process output type Output 1 Option G O 20mA Model 98_A _G _0 0000 Process Output Proportional value de...

Страница 19: ...staterelays change state at zero volts which is zero cross switching They are also optically isolated which means the output circuitry is energized by infrared light striking aphoto sensitive device...

Страница 20: ...listed for the SS switch output The power switching device must provide isolation between the SS switch output and load power since the SS switch output is a non isolated output Minimum load resistan...

Страница 21: ...ore susceptible to electrical interference from loadswitching See Noise Guidelines at the beginning of this chapter 115 Volt Control Power 0 1 Earth Ground Load Power Fuse Ll L2 L1 A A Iif Fuse Y Ef H...

Страница 22: ...four digit display indicating either process actual tem perature the operating parameter values or an open sensor Lower Display Red 0 3 high LED seven segment three or four digit display indicating t...

Страница 23: ...ing the key down decreases the displayed value at a rapid rate New data is self entering in 5 seconds Where To Go From Here AUTO MAN Key Pressed once it clears any latched alarms If the key is pressed...

Страница 24: ...plays the parameters that configure the Series 980 985 s features to your application To enter the Setup Menu press the UP and DOWN keys simultaneously for 3 seconds See Figure 27 The Lower display sh...

Страница 25: ...l point for ail process related data The range is 0 0 0 or 0 00 The default is 0 This parameter only appears if the in parameter is 0 5 or 420 Celsius _ Fahrenheit Selects the units of measure for the...

Страница 26: ...ma Setup Parameters LOC In r S P DEC C F rL rH Otl ot2 ALt LAt SIL rtd Value Range Factory Default 0 3 0 J K appears as H t n J Pt2 rtd rt d 0 5 4 20 Dependent on model number OFF O 5 420 OFF 0 0 0 or...

Страница 27: ...5 F 13 C If the input type is 0 5VDC or 4 20mA the range of Pb1 is 0 999 0 99 9 or O 9 99 determined by the value of DEC The switching differential is 0 03 0 3 or 3 units Pb2 default is 0 Pb2 only app...

Страница 28: ...s page as a master copy for your Series 980 985 Operation Parameters Do not enter any values here make photocopies instead 1 Operation Parameters Value Range Factory Default SP2 rL to rH Same as prima...

Страница 29: ...d as a result of the auto tuning The operator must then establish the cool PID values manually Tuning is complete within 40 minutes Any change of the set point while in auto tune re initiates the auto...

Страница 30: ...you want Rate Adjustment lncrease rA1 to 1 00 min Then raise set point by 20 to 30 F or 11 to 17 C Observe the system s approach to set point If the load temperature overshoots set point increase rA1...

Страница 31: ...F If you change the set point to 130 F the alarms will follow the set point and trip at 137 F and 125 F Alarm Silencing for alarm output A1 is available with the deviation alarm This overrides alarm...

Страница 32: ...Sensor overrange error The sensor input is generating a value that is higher than that allowed for the range of this sensor or the A D circuitry is not functioning properly Enter a valid input Er 2 S...

Страница 33: ...MAN and MODE keys are disabled The UP DOWN keys may be used together to enter the Set Up Menu The alarm output if present will be in its alarm state LED lit The Upper display will read The Lower displ...

Страница 34: ...DOWN keys l Dual digital displays Input Thermocouple RTD and electrical process input Automatic cold junction compensation for thermocouple RTD input 2 or 3 wire platinum 100 ohm 0 C user selectable...

Страница 35: ...ON voltage of 3VDC into a minimum 500 ohm load maximum ON voltage not greater than 32VDC into an infinite load Accuracy l Calibration Accuracy 0 1 of span 1 LSD 77 F 5 F 25 C 3 C ambient rated line vo...

Страница 36: ...on Switched DC open collector non isolated Electromechanical relay Form C 6A Warranted to 100 000 cycles Process 0 10VDC non isolated Process 4 20mA non isolated Process 0 20mA non isolated Process 0...

Страница 37: ...down until the output value is correct The control uses the lower display to prompt the user as to what the input should be Once the input has been properly established and maintained for at least 10...

Страница 38: ...per for correct line voltage See Chapter 2 2 Connect the millivolt source to Terminal 18 Negative and Terminal 20 Positive on the 980 985 terminal strip Use regular 20 24 gauge wire 3 Apply power to t...

Страница 39: ...arm up put the unit in the CAL menu See Figure 33 on Page 37 Press the MODE key until the rL0 prompt is displayed IMPORTANT When the MANUAL LED is ON the unit isautomatlcally calibrating Your sequence...

Страница 40: ...0 24 gauge wire Apply power to the unit and allow it to warm up for 15 minutes After warm up put the unit in the CAL menu See Figure 33 on Page 37 Press the MODE key until the OU prompt is displayed I...

Страница 41: ...rip Use regular 20 24 gauge wire Apply power to the unit and allow it to warm up for 15 15 minutes After warm up put the unit in the CAL menu See Figure 33 on Page 37 Press the MODE key until the 4A p...

Страница 42: ...Page 37 Press the MODE key until the 4A0 prompt is displayed IMPORTANT When the MANUAL LED s ON the unit is automatically calibrating Your sequence is VERY important Always move to the next prompt be...

Страница 43: ...Page 37 Press the MODE key until the 4A0 prompt is displayed IMPORTANT When the MANUAL LED is ON the unit is automatically calibrating Your sequence is VERY important Always move to the next prompt be...

Страница 44: ...d sensing element JIS Japanese Industrial Standards Also Japa nese Industrial Standards Committee JISC Establishes standards on equipment and compo nents Cycle time The time necessary to complete a fu...

Страница 45: ...teristics Displays positive temperature coefficient Set point Intended value of the process variable Switchingsensitivity In ON OFF control the temperature change necessary to change the output from f...

Страница 46: ...r The Series 980 985 13 Wire Input 14 Wire Output 16 I Index 46 Information Resource 6 Inputs 14 Installation Guidelines for Preventing Noise 6 Setup Menu and Parameters 24 Manual Operation 23 31 Mech...

Страница 47: ...val and an RMA number from the Customer Service Department when you are returning an unused product for credit Also we must apply a 20 percent restocking charge for all returned stock controls and acc...

Отзывы: