Ramping Controller Prompt Table
981,
982,
983, 984
Data Communications with the Watlow Series 988 Family
Command Summary Series 981-984, Chapter 5
5.6
ER2
Error,
? <sp> ER2 <cr>
0 = No error
––
Communications
1 = Transmit buffer overflow
2 = Receive buffer overflow
3 = Framing error
4 = Overrun error
5 = Parity error
6 = Talking out of turn
7 = Invalid reply error
8 = Noise error
20 = Command not found
21 = Prompt not found
22 = Incomplete command line
23 = Invalid character
24 = Number of chars. overflow
25 = Input out of limit
26 = Read only command
27 = Write allowed only
28 = Prompt not active
30 = Request to RUN invalid
31 = Request to HOLD invalid
32 = Command invalid in RUN Mode
33 = Command invalid in HOLD Mode
34 = Output 3 is not an Event
35 = Output 4 is not an Event
38 = Asterisk not allowed
39 = Infinite loop error
ERR
Error,
? <sp> ERR <cr>
0 = Errors latching
607
Latching Enable
= <sp> ERR <sp> data.2 <cr>
1 = Errors non-latching
Default: 1
FTR1
Filter Time Constant ? <sp> FTR1 <cr>
-60 to 60 seconds
604
Process Input 1
= <sp> FTR1 <sp> data.2 <cr>
Default: 0
GSD
Guaranteed Soak
? <sp> GSD <cr>
0
°
F to 999
°
F
1205
Deviation
= <sp> GSD <sp> data.2 <cr>
0
°
C to 999
°
C
0 to 999 units
0 = (disabled)
Default: 0
°
F, 0
°
C, or 0 units
HIP
High Power Limit
? <sp> HIP <cr>
LOP (%) to 100%
714
= <sp> HIP <sp> data.2 <cr>
Default: 100 (heat/cool)
Default: 0 (cool only)
HOLD Simulate HOLD
= <sp> HOLD <sp> data.2 <cr>
1 = Holds current file# and step#
1210
Key Press
HUNT Slidewire
? <sp> HUNT <cr>
0.1% to 100.0%
1905
Dead Band %
= <sp> HUNT <sp> data.2 <cr>
Default: 1.0%
HYS1
Output 1 Hysteresis
? <sp> HYS1 <cr>
0
°
F to 999
°
F
507
= <sp> HYS1 <sp> data.2 <cr>
0
°
C to 555
°
C
0 units to 999 units
Default: 3
°
F, 2
°
C, or 3 units
HYS2
Output 2 Hysteresis
? <sp> HYS2 <cr>
0
°
F to 999
°
F
517
= <sp> HYS2 <sp> data.2 <cr>
0
°
C to 555
°
C
720
0 units to 999 units
Default: 3
°
F, 2
°
C, or 3 units
HYS3
Output 3 Hysteresis
? <sp> HYS3 <cr>
0
°
F to 999
°
F
737
= <sp> HYS3 <sp> data.2 <cr>
0
°
C to 555
°
C
0 units to 999 units
Default: 3
°
F, 2
°
C, or 3 units
Table 5.6 -
ER2 to HYS3
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.