Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
Address
Dual Channel Controller Prompt Table
996, 997,
998
, 999
7.10
Data Communications with the Watlow Series 988 Family
Command Summary Series 996-999, Chapter 7
RPA
Ramping Initiation
? <sp> RPA <cr>
0 = off
1100
Channel A
= <sp> RPA <sp> data.2 <cr>
1 = On startup
2 = On startup and set point change
Default: 0
RPB
Ramping Initiation
? <sp> RPB <cr>
0 = off
1104
Channel B
= <sp> RPB <sp> data.2 <cr>
1 = On startup
2 = On startup and set point change
Default: 0
RTA
Ramp Rate
? <sp> RTA <cr>
0 to 9999
°
/minute
1101
Channel A
= <sp> RTA <sp> data.2 <cr>
Default: 100
°
/minute
RTB
Ramp Rate
? <sp> RTB <cr>
0 to 9999
°
/minute
1105
Channel B
= <sp> RTB <sp> data.2 <cr>
Default: 100
°
/minute
RTD1
RTD Calibration
? <sp> RTD1 <cr>
0 = JIS
609
Curve Input 1
= <sp> RTD1 <sp> data.2 <cr>
1 = DIN
Default: 1
RTD2
RTD Calibration
? <sp> RTD2 <cr>
0 = JIS
619
Curve Input 2
= <sp> RTD2 <sp> data.2 <cr>
1 = DIN
Default: 1
SIL3
Alarm 3 Silence
? <sp> SIL3 <cr>
0 = off / disabled
739
= <sp> SIL3 <sp> data.2 <cr>
1 = on / enabled
Default: 0
SRNB Serial Number
? <sp> SRNB <cr>
xxxx =
2
Bottom Display
0000 to 9999
Read the six-digit unit
serial number in two
segments,
"SNxx" and "xxxx,"
i.e., as in the
upper and lower
front panel displays.
SRNT
Serial Number
? <sp> SRNT <cr>
SNxx =
1
Top Display
00 to 99
SOFT
Software Revision
? <sp> SOFT <cr>
0 = Rev A
7 = Rev H
4
1 = Rev B
8 = Rev I
2 = Rev C
9 = Rev J
3 = Rev D
10 = Rev K
4 = Rev E
11 = Rev L
5 = Rev F
12 = Rev M
6 = Rev G
13 = Rev N
etc.
SPA
Set Point Channel A ? <sp> SPA <cr>
RL1 to RH1
300
= <sp> SPA <sp> data.2 <cr>
Default: per IN1 and hardware
SPB
Set Point Channel B ? <sp> SPB <cr>
RL2 to RH2
319
= <sp> SPB <sp> data.2 <cr>
Default: per IN1 and hardware
SP2A
Set Point 2
? <sp> SP2A <cr>
RL1 to RH1
309
Channel A
= <sp> SP2A <sp> data.2 <cr>
Default: per input range
Heat/Heat or
Cool/Cool Only
SP2B
Set Point 2
? <sp> SP2B <cr>
RL2 to RH2
328
Channel B
= <sp> SP2B <sp> data.2 <cr>
Default: per input range
Heat/Heat or
Cool/Cool Only
SYS
Lockout System
? <sp> SYS <cr>
0 = No lockout
1306
Menu
= <sp> SYS <sp> data.2 <cr>
1 = Read only
2 = No read or write
Default: 0
Table 7.10 -
RPA to SP2B
ç
CAUTION:
Avoid writing <=>
continuously,
such as ramping
set points or
repetitive loops, to
the Series 996-999
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the
DEC1, DEC2, IN1
or IN2 setting.