Page 24
Electrical Requirements
E
LECTRICAL
R
EQUIREMENTS
ELECTRICAL REQUIREMENTS
AND PRECAUTIONS
Your
HOT SPRING
spa has been carefully designed to give you
maximum safety against electrical shock. Connecting the spa to an
improperly wired circuit will negate many of the spa’s safety features.
Improper wiring may also cause electrocution, risk of fire, and other
risks of injuries. Please read and follow the electrical installation
requirements and instructions for your spa completely!
SELECTING THE VOLTAGE FOR
YOUR SPA
The
PACE & STRIDE
spas may operate in the following manner:
• 115 volt 20 amp
- the heater will provide approximately 1000
watts of heat only when the pump is operating in LOW speed and
the thermostat is calling for heat (NOTE: The heater does not
operate when the pump is on high speed).
• 115 volt 30 amp
- the heater will provide approximately 1000
watts of heat and will operate while the pump is on low or high
speed.
• 230 volt 30 amp
- the heater will provide approximately 4000
watts of heat only when the pump is operating in LOW speed and
the thermostat is calling for heat (NOTE: The heater does not
operate when the pump is on high speed).
• 230 volt 50 amp -
the heater will provide approximately 4000
watts of heat and will operate while the pump is on low or high
speed.
The
RELAY & RHYTHM
spa models may operate in the following
manner:
• 230 volt 30 amp
- the heater will provide approximately 4000
watts of heat when pump 1 is operating in LOW speed or high
speed and the thermostat is calling for heat (NOTE: The heater
does not operate when pump 2 is on).
• 230 volt 50 amp -
the heater will provide approximately 4000
watts of heat and will operate while both pumps are running.
All electrical connections must be made in accordance with the wiring
information contained in the electrical control box or on the back of the
field wiring access panel of the equipment module.
115 VOLT INSTALLATION (20 amp)
Spas provided with a factory-installed power supply cord with GFCI are
to be plugged into a grounded, grounding type 20 ampere receptacle
(
PACE & STRIDE
) models. No other electrical appliance or fixture can
be used on this circuit.
IMPORTANT:
Under
NO
circumstances should an extension cord be
used. Use of an extension cord will seriously degrade the performance
of the equipment module , can create an electrical hazard and will void
the warranty.
115 VOLT CONVERSION (30 amp)
Refer to the following instructions to convert your 115 volt
PACE &
STRIDE
spa to a 115 volt 30A spa.
NOTE
: Converting the spa should only be done by an authorized
service agent or a qualified electrician. A
HOT SPRING
Spa Technician
must reconfigure spa by pressing and holding the JETS button for 30
seconds followed by pressing the +/- button and change to LL4. Press
the LIGHT button within 25 seconds to save new setting.
A licensed electrician must install the sub-panel (available from your
HOT SPRING
Spa Dealer) to supply power to the spa. The sub-panel
must be placed in sight of the spa, at a minimum distance of 5 feet (1.5
m) away.
L1
N
G
L1
N
G
L2
Power Jumper Position
See Wiring
Illustration
below
115 VAC Wiring
(30A Converted)
Power Jumper must remain
on the Terminal Block to
operate 115 VAC Spa
Models
L1
N
G
115VAC, 30 Amp Single
Pole Circuit Breaker
(Non GFCI)
Main Service
Electrical Panel
Sub-Panel
with GFCI
Breakers
More than 5' (1.5 m)
the Sub-Panel must be
within sight of the spa
Do Not Exceed 50' (15 m)
Control Box
N, Neutral, #10AWG White
L1, Hot, #10AWG Black
Ground, #10AWG Green
Less Than 100' (30
m)
#10 AWG White, Neutral
#10 AWG Green, Ground
#10 AWG Black, L1
WIRING ILLUSTRATION
PERMANENTLY CONNECTED FOR
115 VAC, 30A, 60HZ, CONVERTED MODELS
Power
Jumper
to P21
English
French
Spanish