Line
Function
Setting range
or display
Setting
increment
Basic
setting
740
I
Flow temp setpoint min (for fan convector)
8 °C... Flow temp setpoint max
1 °C
8 °C
741
I
Flow temp setpoint max
Flow temp setpoint min... 70 °C
1 °C
55 °C
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note :
Maximum temperature limitation is not a safety function as required by ground heating.
750
S
Room influence
1%... 100%
1%
50%
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
780
S
Quick setback
Off, Down to reduced setpoint,
Down to frost prot setpoint
Down to
reduced
setpoint
790
S
Optimum start control max
(Early start to switch to the comfort setting.)
0... 360 min
10 min
180 min
791
S
Optimum stop control max (Early stop to switch from
the comfort setting to the reduced setting.)
0... 360 min
10 min
60 min
800
S
Reduced setpoint increase start
-30... 10 °C
1 °C
--
801
S
Reduced setpoint increase end
-30... 10 °C
1 °C
-5 °C
830
S
Mixer valve boost
0 50 °C
1 °C
0 °C
834
S
Actuator running time
30... 873 s
1 s
240 s
850
I
Floor curing function (
)
Off
- Off: Early interruption of the current program, program inactive.
- Functional heating.
- Heating ready for occupation.
- Functional h Curing heating.
- Curing h Functional heating.
- Manually: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
851
I
Floor curing setpoint manually
(if line 850 = manual)
0 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying program stops automatically after running for 25 days.
856
I
Floor curing day current
0 32
857
I
Floor curing day completed
0 32
900
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
1
Protection
mode
Operating mode at end of concrete slab curing period
"
Please comply with the
standards and instructions
of the manufacturer of
the building ! A good
performance of this function
is only possible with an
installation correctly
implemented
(hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting
the adjustment on "Stop"
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
figure 35 - Diagram of the concrete slab curing programs
Heating flow temperature °C
Functional h Curing ready for occupation
Curing ready for occupation
Day
Functional
heating
Installation and operating manual "1532 - EN"
- 39 -
Air to Water Heat Pump