40
|
46
Operating the Manual Override Mode
1
2
3
Use the illustrations and instructions to operate
manual override.
1 On startup, the cylinder is in the low-pressure
mode. This is the default state for the system.
2 When switching to high-pressure mode, the
solenoid valve retracts the cylinder to open the
crossover valve, making the high pressure
discharge available. The proximity sensors on
the cylinder communicate the cylinder position
to the controller, which illuminates the
appropriate mode LED.
3 In the event that high-pressure mode is not
achieved after being selected, the mode LEDs
will flash to indicate an error condition.
Depending on the error condition, you can
achieve high-pressure mode by pressing and
holding the high-pressure side of the switch for
3 seconds, or by tapping the high-pressure side
of the switch 3 times within 3 seconds. The
system then attempts to open the crossover
valve while ignoring the proximity sensors.