TEST THAT THE PRE-TREATMENT SYSTEM IS DELIVERING RO FEED WATER TO 

NECESSARY SPECIFICATIONS BEFORE PLUMBING THE RO SYSTEM ONLINE. 

 

ALWAYS ALLOW NEW SOFTENING SYSTEMS INSTALLED TO PRE-TREAT AN RO SYSTEM 

TO START ON THE BACKWASH/REGENERATION/RINSE CYCLE.  OPERATE THE SOFTENER 

OFF-LINE UNTIL WATER RUNS CLEAR BEFORE USING IT TO PROVIDE RO FEED WATER.  

THIS PROCEDURE ALSO APPLIES TO NEW RESIN BED INSTALLATIONS.  COLOUR THROW 

FROM NEW RESIN BEDS MAY DAMAGE OR FOUL RO MEMBRANES. 

 

WATERITE DOES NOT RECOMMEND THE USE OF A GRANULAR CARBON CARTRIDGE IN 

THE PRE-TREATMENT FILTER HOUSINGS SUPPLIED, FOR THE PRIMARY REDUCTION OF 

CHLORINE.  IT WILL REQUIRE REPLACEMENT TOO OFTEN, LIMIT FLOW RATES AND 

LIKELY LEAD TO CHLORINE BREAKTHROUGH TO THE MEMBRANE ELEMENT.  WE 

RECOMMEND THAT THIS HOUSING BE RESERVED FOR 5-MICRON OR 1-MICRON 

SEDIMENT CARTRIDGES, FOR THE REDUCTION OF SUSPENDED PARTICULATE. 

 

Step 3. Plan your water system 

1. Using a pressure storage tank and pressure switch 

Nominal rates of water production for BlackMaxx™ RB8

 

systems are, at maximum (feed water 

@<500 TDS and 25 degrees Celsius recovery maximum 15%/membrane pH 7.5): 

 

RB820K 

 

20000GPD 

13.8 USGPM  

   52.2 LPM  

0.9 L/s   

   

      

75.7 M3/d 

RB830K

 

30000GPD 

20.8 USGPM 

  78.7 LPM 

1.3L/s 

  113.3 M3/d 

RB840K  

40000GPD

 

27.7 USGPM  

  104.4 LPM 

1.6 L/s 

151.4 M3/d 

RB860K 

60000GPD

 

41.5 USGPM 

  156.6 LPM 

2.51L/s 

227.1 M3/d 

RB880K 

80000GPD

 

 

55.4USGPM 

  209 LPM 

3.3 L/s 

302.8 M3/d 

RB8100K 

100000GPD

 

 

69.4 USGPM 

  262.7 LPM 

4.4 L/s 

378.5 M3/d 

RB8120K 

120000GPD

 

 

83.3 USGPM 

  315.3 LPM 

5.3 L/s 

454.2 M3/d 

RB8150K         

150000GPD

  

104.2 USGPM 

  394.4 LPM  

6.6 L/s 

587.8 M3/d 

RB8180K 

180000GPD

 

125 USGPM 

  473.2 LPM 

7.9 L/s    

681.3 M3/d 

RB8210K 

210000GPD

 

145.8 USGPM 

  551.9 LPM 

9.9 L/s 

794.9 M3/d 

RB8240K 

240000GPD

 

166.6 USGPM 

  630.6 LPM 

 10.5 L/s 

908.4 M3/d

 

 

For many commercial, industrial or municipal requirements, this rate of production will be insufficient 

in periods of peak usage, though over 24 hours the necessary production will be produced.  It will 

be necessary for you to provide product water storage in a non-pressurized tank from which you 

may re-pressurize the water for delivery to your equipment or plumbing system.  Sizing of the tank 

is at the discretion of the end user; however, it should be sized to minimize the starting of the system 

at less than 2 times per hour.  

See appendix for Membrane Temperature Correction Factors.

 

IF THE SYSTEM IS CONNECTED DIRECTLY TO A PRESSURE TANK, MAKE SURE THAT A 

CHECK VALVE IS INSTALLED ON THE PRODUCT WATER LINE BETWEEN THE MACHINE 

OUTLET AND THE PLUMBING SYSTEM PRESSURE SWITCH, TO ELIMINATE 

BACKPRESSURE ON THE MEMBRANE(S).  FAILURE TO DO SO WILL CAUSE PERMANENT 

DAMAGE TO THE RO MEMBRANE(S). 

 

 

Содержание BLACKMAXX RB8

Страница 1: ...T FOR REFERENCE PURPOSES AND TECHNICAL GUIDANCE IT IS STRONGLY RECOMMENDED THAT QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED IN THE EVENT OF AN UNKNOWN INTERRUPTION OF SERVICE OR APPARENT PRODUCT M...

Страница 2: ...molecules are allowed to pass through and collect in the tube while all other mineral and contaminant molecules are rejected and washed from the surface of the membrane to the drain Q What processes...

Страница 3: ...low energy membrane s that are designed to operate at a minimum system pressure of 100 psi 7 0 kg cm and a maximum of 250 psi depending on the model 17 6kg cm Do not attempt to operate your system at...

Страница 4: ...e are highly accurate instruments that have 4 20ma outputs for recording and alarm purposes Calibration of the sensors should be done twice a year Membrane cleaning is a site specific operation Depend...

Страница 5: ...treated to levels 5 mg l to avoid membrane fouling This is usually achieved through the use of organic scavenging ion exchange resin polystyrene or polyacrylic regenerated with salt Chlorine Feed wat...

Страница 6: ...requires The importance of feed water conditions is evident when you examine how crossflow membranes work In simple terms a crossflow filtration system separates an influent stream into two effluent s...

Страница 7: ...ion rate Fouling of membrane surface Softener with organic scavenger resin A Series Fusion RS series Magnum Chlorine 1 ppm Permanent membrane damage Increased salt passage Carbon Filter CF Series Exce...

Страница 8: ...3 3 M3 d RB840K 40000GPD 27 7 USGPM 104 4 LPM 1 6 L s 151 4 M3 d RB860K 60000GPD 41 5 USGPM 156 6 LPM 2 51L s 227 1 M3 d RB880K 80000GPD 55 4USGPM 209 LPM 3 3 L s 302 8 M3 d RB8100K 100000GPD 69 4 USG...

Страница 9: ...RO chemical disinfection is not being used If the permeate is to remain in the tank for a period of more than 1 day without a disinfection residual being added a recirculation loop with a UV disinfec...

Страница 10: ...requirements The RB8 system use a dual voltage configuration to minimize power consumption The system controls are run on a 120 vac 1 amp and the following are ratings for the motors at 230 208 vac 3...

Страница 11: ...re 2b External Electrical Cabinet Motor power 3 PH disconnect Motor starter Flush valve relay Field connection terminals 120vac 24vdc Transformer Main control board 120vac 120 vac control power Manual...

Страница 12: ...n and is capable of delivering the system s necessary feed water flow rate See below for specified feed water flow rate requirements 2 Turn the water supply line to your plumbing OFF Plumb a connectio...

Страница 13: ...um flow requirements on full flow parameters Inlet feed rates will vary with projected system recovery rates Use the following formula to size flow rates according to your specifications Recovery Rate...

Страница 14: ...permeate line should be used Hard plumbing is recommended with either a 304 316 Stainless Steel or PVC line DO NOT USE BLACK IRON PIPE TO CONNECT PERMEATE LINE OR FEEDWATER LINE TO SYSTEM Connect the...

Страница 15: ...olution to sterilize them This can help to prevent any bacteria from contaminating the membranes product core See Figure 5 for membrane housing assembly Disconnect the power and turn off the feed wate...

Страница 16: ...e lines Ensure the gaskets are in good repair Replace if necessary Turn power and water back on Start unit Fix any leaks 3 7 3 Membrane removal To remove the membrane from the housing remove the end c...

Страница 17: ...point Allow the feed water to fill slowly into the system This process will expedite the air removal from the RO system Once the water starts to run out of the system to drain close the auto flush va...

Страница 18: ...ce after about 48 to 72 hours of operation You should develop a daily log to track line pressure system pressure feed water TDS permeate TDS permeate flow rate and waste flow rate This will allow you...

Страница 19: ...s kit This is needed to claim any parts or repair service during the warranty period Read the document completely for warranty claim instructions Your RB8 BlackMaxx system comes with a limited one yea...

Страница 20: ...to tightening Replace gasket Threaded fittings leaking Disassemble remove old Teflon tape apply new tape re assemble Pre filter housing leaking Tighten clamp handle Remove cap and Inspect o rings for...

Страница 21: ...nk full Drain Tank start in auto mode Low inlet pressure Check pre treatment system water quality Inlet valve closed System in alarm Check alarm status Pumps cavitating See low feed pressure System of...

Страница 22: ...onductivity Probe ROSCOND VALVES Part Description Part 1 0 SS Globe Valve 20 30 40K AK200UJM100 1 25 SS Globe Valve 60 80K AK200UJM125 1 5 SS Globe Valve 100 120K AK200UJM150 1 00 Check Valve Poppet S...

Страница 23: ...23 Section 9 RB8 BLACKMAXX Performance Log Date Feed System Permeate Feed Water Permeate Reject Permeate Waste Pressure Pressure TDS TDS Flow Meter Flow Meter Totalizer Totalizer...

Страница 24: ...24 Date Feed System Permeate Feed Water Permeate Reject Permeate Waste Pressure Pressure TDS TDS Flow Meter Flow Meter Totalizer Totalizer...

Страница 25: ...llowing is meant as a guide for determining the output of your BlackMaxx RB8 system Locate your model number and then look for the approximate temperature of your feed water This will give the estimat...

Страница 26: ......

Отзывы: