background image

18

SPECTRA COMMERCIAL AND RESIDENTIAL INSTALLATION GUIDE

9)

Initiate a control signal to place the unit in the heating mode.  Heating set point must

be set above room temperature.

10) First stage heating will energize after a time delay.

11) Check the temperature of both the supply and discharge water.  Refer to Table 2 on

page 17.

12) Check for an air temperature rise of 20

°

 to 35

°

 F across the air coil, depending on the

fan speed and entering water temperature.  Refer to Unit Operating Pressure on

page 13.

13) If auxiliary electric heaters are installed, adjust the heating set point until the electric

heat banks are sequenced on.  All stages of the auxiliary heater should be sequenced

on when the thermostat is in the "Emergency" Heat mode.  Check amperage of

each element.

14) Adjust the heating set point below room temperature and verify that the compressor

and water valve or loop pumps deactivate.

15) During all testing, check for excessive vibration, noise or water leaks.  Correct or repair

as required.

16) Set system to desired normal operating mode and set temperature to maintain desired

comfort level.

17) Instruct the owner/operator of the proper operation of the thermostat and system

maintenance.

18) During all testing, check for excessive vibration, noise or water leaks.  Correct or repair

as required.

19) Set system to desired normal operating mode and set temperature to maintain desired

comfort level.

20) Instruct the owner/operator of the proper operation of the thermostat and system

maintenance.

NOTE: If performance during any mode appears abnormal, refer to the troubleshooting
section on page 19.

Water Coil Maintenance

1)

Keep all air out of the water. An open loop system should be checked to insure that the

well head is not allowing air to infiltrate the water line. Lines should always be airtight.

2)

Keep the system under pressure at all times. It is necessary in open loop systems that

the water control valve be placed in the discharge line to prevent loss of pressure

during off cycles. Closed loop systems must have positive static pressure or air vents

may draw air into the system.

NOTE: 

If the installation is performed in an area with a known high mineral content (125

P.P.M.or greater) in the water, it is best to establish with the owner a periodic maintenance
schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary,
use standard coil cleaning procedures which are compatible with either the cupronickel or
copper water lines. Generally, the more water flowing through the unit the less chance
for scaling.

Other Maintenance

Filters - Filters must be clean to obtain maximum performance. They should be in-

spected every two to three months under normal operating conditions and be replaced

when necessary. Units should never be operated without a filter.

Preventive

Maintenance

Содержание SPECTRA SX Series

Страница 1: ...s for shipping damage removing the units from the cartons if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the d...

Страница 2: ...side or end discharge and may be field converted from one to the other by replacing the discharge panel The new panel must be ordered Horizontal units are normally suspended from a ceiling by four 3...

Страница 3: ...ase isolated from the ceiling joists by additional layers of vibration absorbing mesh Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a d...

Страница 4: ...connector has a rubber gasket seal similar to a garden hose gasket which when mated to the flush end of any 1 threaded pipe provides a leak free seal without the need for thread sealing tape or compo...

Страница 5: ...nsate drain assembly consists of a drain tube which is connected to the drain pan a 3 4 PVC female adapter and a flexible connecting hose The female adapter may exit either the front or the side of th...

Страница 6: ...e brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished Cleaning and Flushing Prior to start up of any heat pump the water circulating...

Страница 7: ...t up Obtain these forms from your commercial representative or contact WaterFurnace Ground Source Systems Once piping is completed between the unit flow center and the ground loop Figure 7 on page 8 f...

Страница 8: ...be disposed of in various ways depending on local building codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Co...

Страница 9: ...r faucet 5 Flush the tank by opening the cold water inlet valve to water heater to free the tank of sediments Close when draining water is clear 6 Disconnect the garden hose and remove the drain valve...

Страница 10: ...faces of both connecting water lines with 3 8 wall closed cell insulation Figure 9 Water Heater Connection Kit Cold Drain Valve Coaxial Drain Tee In Out P T Relief Valve Long Elbow Venting Waste Valve...

Страница 11: ...age heat 3 DHW pump should be running Be sure DHW pump disable switch SW1 2 is ON refers to commercial microprocessor only 4 The temperature difference between water entering and leaving the desuperhe...

Страница 12: ...al strip PS and contactor CC Figure 12 Spectra SX Line Voltage Blower Relay Compressor Control Module Transformer Compressor Contactor Ground Lug Typical Electromechanical Control Box Configuration Te...

Страница 13: ...0 60 28 3 34 2 50 50 208 230 60 3 197 254 21 0 13 5 99 0 4 6 18 1 21 4 30 30 460 60 3 414 506 11 5 7 4 49 0 2 3 9 7 11 5 15 15 575 60 3 518 633 9 0 5 8 40 0 2 3 8 1 9 5 15 15 SX068 208 230 60 1 197 25...

Страница 14: ...3 Air flow Settings 4 L2 Orange Factory low voltage wiring Legend Switch High pressure Switch Low pressure Relay coil Temperature Limit Switch Field wire lug Ground Relay Contacts N O N C Polarized c...

Страница 15: ...pressure Polarized connector Condensate Overflow Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Optional block Internal junction Quick conne...

Страница 16: ...M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L 590 570 560 550 545 540 530 520 510 500 H 790 780 775 770 765 760 740 720 690 670 610 SX019 M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L...

Страница 17: ...ble 3 6 Check the temperature of both the supply and discharge water Refer to Start Up Performance Table 2 7 Check for an air temperature drop of 15 to 25 F across the air coil depending on the fan sp...

Страница 18: ...tem to desired normal operating mode and set temperature to maintain desired comfort level 20 Instruct the owner operator of the proper operation of the thermostat and system maintenance NOTE If perfo...

Страница 19: ...t mode Check thermostat and field control wiring If steps above show that the unit control board is not indicating proper results i e LED indication replace board If LEDs are indicating properly repla...

Страница 20: ...without notice WaterFurnace is a registered trademark and Spectra is a trademark of WaterFurnace International Inc 1999 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 P...

Отзывы: