10
SPECTRA COMMERCIAL AND RESIDENTIAL INSTALLATION GUIDE
4)
Run interconnection copper tubing (1/2”
nominal). The recommended maximum
distance is 50 ft. between the unit and water
heater (see Figures 10 and 11).
5)
To prevent air entrapment in the system, install
a vent coupling at the highest point of the
interconnecting line.
6)
Insulate all exposed surfaces of both
connecting water lines with 3/8" wall
closed cell insulation.
Figure 9 -
Water Heater Connection Kit
Cold
Drain Valve
Coaxial
Drain Tee
In
Out
P/T Relief
Valve
Long
Elbow
Venting
Waste Valve
or Vent
Coupling
Drain Valve
P/T Relief
Valve
Hot
Do not connect electrical to pre-heat tank.
Figure 11 -
Desuperheater Installation
Preheat Tank
Drain Valve
Coaxial
Drain Tee
In
Out
P/T Relief
Valve
Long
Elbow
Venting
Waste Valve
or Vent
Coupling
Hot
Cold
Water In
Cold
Figure 10 -
Typical Desuperheater Installation
for Units with Internal Pumps