WaterFurnace SPECTRA SX Series Скачать руководство пользователя страница 13

13

SPECTRA COMMERCIAL AND RESIDENTIAL INSTALLATION GUIDE

Compressor

Fan 

Model

Rated

Voltage

Motor

Total Unit

Min. Circuit

Max.

Max. HACR

Total Unit

Min. Circuit

Max.

Max. HACR

Voltage

Min./Max.

MCC

RLA

LRA

FLA

FLA

Ampacity

Fuse*

Breaker*

FLA

Ampacity

Fuse

Breaker

SX010

208-230/60/1

197/254

6.9

4.4

23.0

0.6

10.8

11.9

15

15

5.0

6.1

10

10

265/60/1

239/292

4.6

2.9

16.0

0.6

-

-

-

-

3.5

4.3

6

6

SX013

208-230/60/1

197/254

7.4

4.7

27.0

0.6

11.1

12.3

15

15

5.3

6.5

10

10

265/60/1

239/292

5.4

3.5

22.0

0.6

-

-

-

-

4.1

4.9

6

6

SX016

208-230/60/1

197/254

9.2

5.9

29.0

1.1

12.8

14.3

20

20

7.0

8.5

10

10

265/60/1

239/292

8.5

5.4

27.0

1.0

-

-

-

-

6.4

7.8

10

10

SX019

208-230/60/1

197/254

11.0

7.1

38.0

1.1

14.0

15.7

20

20

8.2

9.9

15

15

265/60/1

239/292

8.6

5.5

32.0

1.0

-

-

-

-

6.5

7.9

10

10

SX024

208-230/60/1

197/254

14.6

9.4

49.0

1.2

16.4

18.7

25

25

10.6

12.9

20

20

265/60/1

239/292

12.8

8.2

44.0

1.1

-

-

-

-

9.3

11.4

15

15

SX030

208-230/60/1

197/254

15.3

9.8

56.0

1.5

17.1

19.6

25

25

11.3

13.8

20

20

265/60/1

239/292

13.8

8.8

55.0

2.0

-

-

-

-

10.8

13.1

20

20

208-230/60/3

197/254

10.5

6.7

51.0

1.5

-

-

-

-

8.2

9.9

15

15

460/60/3

414/506

5.4

3.5

25.0

1.1

-

-

-

-

4.6

5.4

6

6

SX036

208-230/60/1

197/254

21.4

13.7

75.0

2.2

21.7

25.1

35

35

15.9

19.3

30

30

265/60/1

239/292

19.4

12.4

73.0

2.0

-

-

-

-

14.4

17.5

25

25

208-230/60/3

197/254

14.0

9.0

68.0

2.2

-

-

-

-

11.2

13.4

20

20

460/60/3

414/506

6.7

4.3

34.0

1.1

-

-

-

-

5.4

6.5

10

10

SX042

208-230/60/1

197/254

22.5

14.4

82.0

2.8

23.0

26.6

40

40

17.2

20.8

35

35

208-230/60/3

197/254

14.0

9.0

70.0

2.8

-

-

-

-

11.8

14.0

20

20

460/60/3

414/506

7.1

4.6

33.0

1.4

-

-

-

-

6.0

7.1

10

10

575/60/3

518/633

5.3

3.4

27.0

1.4

-

-

-

-

4.8

5.6

6

6

SX048

208-230/60/1

197/254

26.6

17.1

105.0

3.5

26.4

30.6

45

45

20.6

24.8

40

40

208-230/60/3

197/254

16.7

10.7

85.0

3.5

-

-

-

-

14.2

16.9

30

30

460/60/3

414/506

8.2

5.3

42.0

1.8

-

-

-

-

7.1

8.4

10

10

575/60/3

518/633

6.7

4.3

34.0

1.8

-

-

-

-

6.1

7.2

10

10

SX058

208-230/60/1

197/254

37.0

23.7

129.0

4.6

34.1

40.0

60

60

28.3

34.2

50

50

208-230/60/3

197/254

21.0

13.5

99.0

4.6

-

-

-

-

18.1

21.4

30

30

460/60/3

414/506

11.5

7.4

49.0

2.3

-

-

-

-

9.7

11.5

15

15

575/60/3

518/633

9.0

5.8

40.0

2.3

-

-

-

-

8.1

9.5

15

15

SX068

208-230/60/1

197/254

45.0

28.8

169.0

5.9

40.5

47.8

70

70

34.7

42.0

70

70

208-230/60/3

197/254

27.0

17.3

123.0

5.9

-

-

-

-

23.2

27.5

40

40

460/60/3

414/506

14.0

9.0

62.0

3.0

-

-

-

-

12.0

14.2

20

20

575/60/3

518/633

11.0

7.1

50.0

3.0

-

-

-

-

10.1

11.8

15

15

   *Includes 5.4 amperage allowance for source side loop pump (up to 1/2 H.P.) 

    and 0.4 amperage allowance for desuperheater circulating pump operation.

    Always refer to unit nameplate data prior to installation.

   HACR circuit breaker in United States only.  All fuses are class RK-5.

Commercial

Residential

Unit Electrical
Data

Unit Operating Pressures*

Cooling**

Heating - No Desuperheater

Entering

Water

Suction

Discharge

Water

Air

Suction

Discharge

Water

Air

Water

Flow

Pressure

Pressure

Super-

Sub-

Temp

Temp

Pressure

Pressure

Super-

Sub-

Temp

Temp

Temp 

°

F

GPM

PSIG

PSIG

heat

cooling

Rise 

°

F

Drop 

°

F DB

PSIG

PSIG

heat

cooling

Drop 

°

F DB

Rise 

°

F

1.5

61-70

100-117

25-35

15-25

21-24

21-26

34-39

163-183

8-12

5-9

7.6-8.4

14-20

30

2.3

62-71

92-109

25-35

15-25

13-16

21-26

37-42

165-185

8-12

5-9

4.8-5.6

16-22

3.0

62-71

88-104

25-35

15-25

6-11

21-26

38-44

167-186

8-12

5-9

3.4-4.2

16-22

1.5

79-85

145-170

15-21

12-25

20-23

20-25

51-58

175-202

10-15

5-9

10.8-11.9

23-29

50

2.3

75-83

130-155

15-21

12-25

12-15

20-25

53-62

178-206

10-15

5-9

6.7-8.1

24-30

3.0

72-82

125-150

15-21

12-25

8-12

20-25

55-65

180-208

10-15

5-9

5.1-5.9

25-31

1.5

78-88

180-200

 12-18

13-18

19-22

19-24

71-82

215-250

15-24

3-7

14.0-15.2

28-34

70

2.3

78-90

169-187

 12-18

13-18

11-14

19-24

77-89

203-235

15-24

3-7

9.0-10.2

30-37

3.0

78-91

160-180

 12-18

13-18

7-12

19-24

81-92

200-235

15-24

3-7

6.7-7.9

31-38

1.5

79-92

230-272

 12-18

13-18

18-21

17-23

-

-

-

-

-

-

90

2.3

80-93

215-248

 12-18

13-18

10-14

17-23

-

-

-

-

-

-

3.0

80-93

208-240

 12-18

13-18

6-11

17-23

-

-

-

-

-

-

*Based on Nominal 400 cfm per ton airflow and 70

°

F EAT htg. and 80/67

°

F EAT cooling.

**Cooling air and water numbers can vary greatly with changes in humidity.

Содержание SPECTRA SX Series

Страница 1: ...s for shipping damage removing the units from the cartons if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the d...

Страница 2: ...side or end discharge and may be field converted from one to the other by replacing the discharge panel The new panel must be ordered Horizontal units are normally suspended from a ceiling by four 3...

Страница 3: ...ase isolated from the ceiling joists by additional layers of vibration absorbing mesh Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a d...

Страница 4: ...connector has a rubber gasket seal similar to a garden hose gasket which when mated to the flush end of any 1 threaded pipe provides a leak free seal without the need for thread sealing tape or compo...

Страница 5: ...nsate drain assembly consists of a drain tube which is connected to the drain pan a 3 4 PVC female adapter and a flexible connecting hose The female adapter may exit either the front or the side of th...

Страница 6: ...e brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished Cleaning and Flushing Prior to start up of any heat pump the water circulating...

Страница 7: ...t up Obtain these forms from your commercial representative or contact WaterFurnace Ground Source Systems Once piping is completed between the unit flow center and the ground loop Figure 7 on page 8 f...

Страница 8: ...be disposed of in various ways depending on local building codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Co...

Страница 9: ...r faucet 5 Flush the tank by opening the cold water inlet valve to water heater to free the tank of sediments Close when draining water is clear 6 Disconnect the garden hose and remove the drain valve...

Страница 10: ...faces of both connecting water lines with 3 8 wall closed cell insulation Figure 9 Water Heater Connection Kit Cold Drain Valve Coaxial Drain Tee In Out P T Relief Valve Long Elbow Venting Waste Valve...

Страница 11: ...age heat 3 DHW pump should be running Be sure DHW pump disable switch SW1 2 is ON refers to commercial microprocessor only 4 The temperature difference between water entering and leaving the desuperhe...

Страница 12: ...al strip PS and contactor CC Figure 12 Spectra SX Line Voltage Blower Relay Compressor Control Module Transformer Compressor Contactor Ground Lug Typical Electromechanical Control Box Configuration Te...

Страница 13: ...0 60 28 3 34 2 50 50 208 230 60 3 197 254 21 0 13 5 99 0 4 6 18 1 21 4 30 30 460 60 3 414 506 11 5 7 4 49 0 2 3 9 7 11 5 15 15 575 60 3 518 633 9 0 5 8 40 0 2 3 8 1 9 5 15 15 SX068 208 230 60 1 197 25...

Страница 14: ...3 Air flow Settings 4 L2 Orange Factory low voltage wiring Legend Switch High pressure Switch Low pressure Relay coil Temperature Limit Switch Field wire lug Ground Relay Contacts N O N C Polarized c...

Страница 15: ...pressure Polarized connector Condensate Overflow Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Optional block Internal junction Quick conne...

Страница 16: ...M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L 590 570 560 550 545 540 530 520 510 500 H 790 780 775 770 765 760 740 720 690 670 610 SX019 M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L...

Страница 17: ...ble 3 6 Check the temperature of both the supply and discharge water Refer to Start Up Performance Table 2 7 Check for an air temperature drop of 15 to 25 F across the air coil depending on the fan sp...

Страница 18: ...tem to desired normal operating mode and set temperature to maintain desired comfort level 20 Instruct the owner operator of the proper operation of the thermostat and system maintenance NOTE If perfo...

Страница 19: ...t mode Check thermostat and field control wiring If steps above show that the unit control board is not indicating proper results i e LED indication replace board If LEDs are indicating properly repla...

Страница 20: ...without notice WaterFurnace is a registered trademark and Spectra is a trademark of WaterFurnace International Inc 1999 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 P...

Отзывы: